Specifications

System Operation
150972 8-5
8.4.4 Conduct a Fire Drill
1. From the User or Installer Menu, press for System Tests.
2. Press for Fire Drill. You will be prompted to press .
3. The drill will begin immediately after you press .
4. Press any key to end the drill. (If you do not press any key to end the fire drill manually, it
will time out automatically after one hour.)
If a fire drill switch has been installed, activating the switch one time will begin the drill;
activating a second time will end the drill.
8.4.5 Conduct an Indicator Test
The indicator test checks the annunciator LEDs, PZT, and LCD display.
1. From the Installer Main Menu, press for System Tests.
2. Press for Indicator Test. The system turns on each LED several times, beeping the PZT
as it does so. At the same time it scrolls each available character across the LCD. A prob-
lem is indicated if any of the following occurs:
An LED does not turn on;
You do not hear a beep;
All four lines of the LCD are not full.
This test takes approximately 15 seconds to complete. You can press any key to end manually
while the test is still in progress. When the test ends, you will be returned to the <Test Menu>.
1
1
ENTER
ENTER
1
2