7.5.6 Miscellaneous Options
Through this programming option you can set the water flow delay time, low AC report delay,
enable or disable automatic daylight savings time adjustment, clock format, and AC clock
frequency.
7.5.6.1 Water Flow Delay
You can program a delay of 0-90 seconds (zero means no delay) to be used in conjunction
with a water flow switch. The delay is system-wide. All water flow switches on the system
will use the same delay period.
To access the screen for programming water flow delay, follow these steps:
1. Enter the installer code.
2. Press to display the installer menu.
3. Select for Program Menu.
Display reads: ,QLWLDOL]LQJ
3OHDVHZDLW
4. Select for System Options.
5. Select for Miscellaneous Options.
A screen similar to the one shown in Figure 7-18 will display.
Figure 7-18 Water Flow Delay Programming Screen
6. Enter the number of seconds (0 to 90 ) to delay an a water flow switch alarm, then press
.
7
5
6
Delay in seconds
before waterflow
alarm occurs.
(00 - 90)