Specifications
Programming
150972 7-9
Example or Zone Mapping:
Suppose you want to program Zone 1 so that:
• Any alarm (detector, water flow or manual pull) would activate Output Group 1 using the
ANSI cadence pattern.
• Manual pull alarm would activate Output Group 3 using constant output.
• Troubles would activate Output Group 2 using the zone-coded cadence pattern.
To accomplish this you need to access the screen for each event and then select your output
groups. Figure 7-4 shows how you would program this application.
Figure 7-4 Zone Mapping Example