This section of the manual manually program the IntelliKnight control panel. Each subsection
discusses these menu options in detail. All options described in this section can be performed
using the IntelliKnight 5590 downloading software.
7.1 Modules
This section lists the options available under the module option in the program menu. The
types of modules available for the 5820 control panel are, 5815 (SLC), 5860 (Keystation),
5824 (Serial/Parallel input/output), 5895 (Input/output Power Supply), 5880 (LED Input/
Output module), and a 5865 (LED Annunciator).
7.1.1 Edit Modules
The features that can be edited when this option is selected are, module name, and class of
wiring (Class A or Class B).
To edit an existing module, follow these steps:
1. Enter the installer code.
2. Press to display the installer menu.
3. Select for Program Menu.
Display reads: ,QLWLDOL]LQJ
3OHDVHZDLW
4. Press to enter module menu.
5. Press to edit a module.
6. Use the or arrow to select the module you wish to edit.
Important!
Before any customized programming is done, JumpStart should be run first. After
JumpStart is run, thoroughly test the system. The reason the system should be tested
after JumpStart is because Jumpstart automatically programs the system, searching for
and configuring all SLC and SBUS devices it finds. JumpStart allows you to confirm
the integrity of the installation prior to performing any custom programming. After
determining that the hardware is properly installed, custom programming can be
performed. Refer to Section 6.