Specifications

SLC Device Installation
150972 5-7
5.7 Relay Module Installation
The information in this section applies to Model SD500-ARM Relay Modules. See Section
5.10.2 for information on how to use the on-board dipswitch to select an address for the
module.
5.7.1 Electrical Specifications
The following is electrical rating information for SD500-ARM relay modules.
Relay Ratings
30 VDC @ 2.0 A Resistive
30 VDC @ 1.0 A Inductive (.6PF)
30 VDC @ .6 A (.35PF) Pilot Duty
Connect to power limited sources only.
5.7.2 Wiring
Wire relay modules to the panel or to the 5815 as shown in Figure 5-7.
Figure 5-7 Relay Module Connection to the FACP (Class B)
5820
or
5815
SD500-ARM
Supervised
Power Limited