Specifications

150972 5-1
Section 5
SLC Device Installation
5.1 Types of SLC Devices
The following types of SLC devices can be used with the 5820 system.
*Model SD500-AIM Input Module (switch input), standard size, dipswitch configurable
*Model SD500-MIM Mini Input Monitor Module (switch input), small size, dipswitch
configurable. Fits in single-gang box with manual pull station switch.
*Model SD500ARM Addressable Relay Module, dipswitch configurable
Model SD505-AHS Heat Sensor
Model SD505-AIS Ionization Smoke Detector
Model SD505-APS Photoelectric Smoke Detector
Model SD505-ADH Duct Housing (used with SD505-AIS or SD505-APS smoke detec-
tors)
Model SD500-ANM Addressable Notification Module
* Indicates replacement for earlier model. SD500-AIM replaces SD500-FRCM-4; SD500-MIM replaces
SD500-FRCM; SD500-ARM replaces SD505-ARM. Earlier models are compatible with the panel but are no
longer manufactured by Silent Knight. Contact Silent Knight if you need information about these models.
5.2 Maximum Number of Devices
A total of 381 analog addressable devices can be used with the IntelliKnight 5820 system. 127
devices can be attached to the main 5820 system. The optional Model 5815 SLC Expander
can add another 127 devices. Up to two 5815s can be added to the main system to achieve the
381 point capacity.
Caution
To avoid the risk of electrical shock and damage to the unit, power should be OFF at the control panel while
installing or servicing.