Specifications

Control Panel Installation
150972 4-43
4.16 Model 5220 Direct Connect Module
The 5220 Direct Connect Module can be used with the 5820 to meet NFPA 72 standards. The
5220 requires four connections to the 5820 and provides outputs for city box and polarity
reversal applications. The 5220 cannot be used for sprinkler supervisory.
The 5220 provides a current that reverses polarity during an alarm or removes current during a
trouble condition.
Figure 4-41 Shows the specific components of the 5220 module which will be used for
installation.
Figure 4-41 5220 Components
4.16.1 5220 Electrical Specifications
T shows the electrical specifications for the 5220 for different wiring configurations.
* Notification supervision current accounted for in 5820 draw.
Table 4-4: 5220 Electrical Specifications
Wiring Configuration Standby Current Alarm Current Comment
City Box
*0 1 Amp for 1 second See Section 4.16.2 for
wiring diagram.
Polarity Reversal 100 mA 100 mA See Section 4.16.3 for
wiring diagram.
R10
Earth
Ground
4-Pin
Connector
For Cable
(P/N 130294)
Terminal Block