Specifications
Control Panel Installation
150972 4-41
4.15 Keltron Model 3158 Installation
The IntelliKnight 5820 is compatible with Keltron Model 3158, used for direct connection to
a Keltron receiver. The 3158 reports alarms, supervisories, and troubles.
The steps for connecting the 3158 to the 5820. Refer to the 3158 installation instructions for
complete information.
1. Wire the 3158 to the 5820 as shown in the connection list and Figure 4-40.
2. Wire the 3158 within 20 feet of the 5820. Wiring must be enclosed in conduit.
3. Program 5820 Relay 1 for alarm.
4. Program I/O 5 for alarm.
5. Program I/O 6 for supervisory.
Table 4-3: Keltron 3158 to IntelliKnight 5820 Connection List
Terminal # Connects To Terminal # Connects To
3158 Term. 1 To Keltron receiving equipment 3158 Term. 8 5820 Term. 28
3158 Term. 2 To Keltron receiving equipment 3158 Term. 9 5820 Term. 5
3158 Term. 3 Earth ground 3158 Term. 10 5820 Term. 4
3158 Term. 4 Not used; no connection. 5820 Term. 6 5820 Term. 29
3158 Term. 5 5820 Term. 18 5820 Term. 28 5820 Term. 31
3158 Term. 6 5820 Term. 19 5820 Term. 29 5820 Term. 30
3158 Term. 7 5820 Term. 7