Addressable relay modules
Assign addressable relay modules to output groups through programming.
(JumpStart assigns all relay modules to Group 1.)
7.4
LED output points (from the 5880 LED Driver or 5865/66 LED Annunciator)
Assign LED modules to output groups through programming. 7.4.3
All output circuits (1-8):
Disable (set to UNUSED) any unused circuits. If you do not disable unused
output circuits, they will cause a trouble condition (unless an EOL resistor
is used).
7.4
Select a name for the point, if desired. 7.4
Output Group Configuration
Add the group to the system if it does not already exist. 7.3.2
Assign output points to the group. 7.4
Program a name (or description) for the group, if desired. 7.3.1.1
Select “group properties” (see below).
Latching / non-latching 7.3.1
Silencing option 7.3.1
Select options for activation with system switches. 7.3.1
Map zones to output groups that will activate when zone goes into alarm. 7.2.1.3
Select a cadence pattern for outputs in the zone. 7.2.1.3