Specifications
Model SK-4224 Fire Control Panel Installation/Operation Manual
6-2 151068
To Enable For Entire Panel (DIP 3) DIP Position
Serial Accessory Devices
SW5
ON = Serial Annunciator connected to the control panel.
OFF = No Serial Annunciator connected to the control
panel.
SW6
ON = Serial DACT connected to the control panel
OFF = No Serial DACT connected to the control panel.
AC loss report delay SW7
ON = 6 hour delay on AC loss report.
OFF = No delay on AC.
Note: If there is not a serial DACT connected to the
control panel this should be set to the OFF
position.
Input Output Circuits Class A / Class B Enable SW8
ON = Class A configuration for both the input and
output circuits.
OFF = Class B configuration for both the input and
output circuits.
Table 6-1: System Configuration