Installation guide
Section 1 - Description of the Control Panel 7
keypad and will send a “zone alarm” code. It is intended for connecting detectors
not related to the burglary alarm, such as gas or flooding sensors, etc.
10 - 24H SILENT -
armed all the time, irrespective of whether the partition it is assigned to
is armed, or not. Violation of this zone will only send a “zone alarm” code to the
monitoring station.
11 - 24H FIRE -
armed all the time, irrespective of whether the partition it is assigned to is
armed, or not; intended to manage the fire detectors.
If the control panel contains a zone programmed as the "fire power supply",
violation of the zone will actuate the alarm verification mechanism and will signal
alarm in the keypad. To perform the verification, disconnect momentarily power
supply to the fire detectors and check, whether after reconnection of power supply
the violation will be repeated within 90 seconds. If that’s the case, the control panel
will send a „zone alarm” message to the monitoring station, activate the “fire alarm”
outputs, and trigger the fire alarm (intermittent signal) in the keypad.
If there are no fire detector supply zones, the zone violation will immediately send a
„zone alarm” code to the monitoring station, activate the "fire alarm"
and "fire/burglary alarm " type outputs, as well as trigger the fire alarm (intermittent
signal) in the keypad
.
12 - ARMING
- violation of this zone will arm the partitions the zone belongs to
.
13 - SILENT ARMING
- violation of this zone will arm in silent mode the partitions the zone
belongs to.
14 - DISARMING
- violation of this zone will disarm the partitions the zone belongs to.
15 - NO ALARM ACTION -
violation of this zone will activate the "zone violation" type
outputs.
16 - ARMING/DISARMING
– controls arming/disarming of partition to which this zone is
assigned. Setting of "PRIORITY" option allows to choose one of two different
modes:
- PRIORITY option enabled: zone violation will arm the partition, while end of
violation will disarm the partition ("Bistable" action)
- PRIORITY option disabled: each violation of the zone will trigger partition's state
between "Armed" and "Disarmed" state ("Monostable" action).
17 - DELAY AUDIBLE
– a delayed zone with the delay countdown signaling in keypads.
18 - AUTOMATIC BYPASS ARMING
– violation of this zone arms the partition the
zone belongs to, simultaneously bypassing the zones programmed as AUTO-
BYPASS (see service functions 16,17,18,19)
19 - PERIMETER –
zone armed since entering the access code and confirming it with the
[#] key (i.e. arming the partition). Violation of this zone during countdown of the „exit
delay” will trigger an alarm.
20 -
ENTRY/EXIT-FINAL
– acts much like the type 0 (entry/exit) zone, but the violated
zone RESTORE during exit delay countdown will stop the countdown and begin the
partition armed mode.
Reaction time for each zone can be programmed within 0.016 s to 4.08 s.
For each of the delayed zones, an individual time delay can be set.
Each zone involves a few options to determine the reaction in particular situations.
It is possible to determine for each zone the maximum violation time (in seconds),
after which the zone will be recognized by the control panel as defective, and to
determine the maximum "no violation" time (in hours), after which the zone will be
recognized by the control panel as defective.
The zones can be selectively bypassed.
Seven event codes to be sent to the monitoring stations can be determined for each
zone.