Installation guide

80 Appendix C - Technical Data
Table 1. Example of panel power supply load estimation and battery selection.
No. Loads Max current Mean current consumption
1
Main board CA-10
70mA 70mA
2 Keypads (2 LCD + 2 LED)
520mA 200mA
3 Outputs OUT1...OUT3
3 x 2.2A ** 2A
4 Output OUT 4 (detectors 15 pcs.*)
15 x 20mA 15 x 20mA
5 Outputs OUT 5...OUT 6
2 x 50mA 50mA
6 Battery charging current
1000mA -
Total max current consumption by the system
with no alarm signaling
I = 70mA+520mA+300mA+100mA+1000mA
=1990mA
Battery selection based on max. and mean
current consumption by the system, assumed
duration of power trouble 12h, assumed 1
alarm with 15 min (0.25h) duration of signaling
A
Max
= 1.25x(0,07x12+0,52x12+0,3x12+0,1x0,25+
+6,6x0,25) = 1,25 x 12,355
15,44Ah
A
Av
= 1.25x(0,07x12+0,2x12+0,3x12+0,05x0,25+
+2x0,25) = 1,25 x 7,35
9,19Ah
Recommended standby power supply: battery 12V /17Ah
*
Assumed current consumption by a single detector 20mA.
**
In case, where the capacity of the power supply is exceeded, the current is supplied by battery.
NOTES:
y
The control panel power supply unit has been designed for work with lead
batteries or other batteries with a similar charging curve (European Directives
91/157/EEC and 83/86/EEC).
yIt is impermissible to connect a fully discharged battery (voltage on terminals
without a load less than 11V) to the alarm panel. To avoid hardware damage,
fully discharged or never used battery should be charged initially using proper
charger.
IMPORTANT: The SATEL Company recommends that operation of the whole alarm system be
regularly tested. However, a reliable alarm system does not prevent burglary,
assault or fire from happening, it only diminishes the risk that such a situation
will cause no alarm or notification.