Installation guide

Section 4 - Programming – Service Functions 71
Option 1 disables the possibility of arming, if the control panel has detected a
battery trouble.
When selected, the option 2 will reset the counters of the zones bypassed after 1
or 3 alarms at 00:00 hour.
Selecting the Option 3 makes the TS only available in the keypad it was called
from, while in the keypads of other partitions the TS is disabled.
Option 4 activates the function of displaying service message after tamper alarm
until service intervention (using of service code).
Selecting the Option 5 results, in the event of trouble, in the keypad LED signaling
trouble until the trouble memory review function (key [7]) is called and ended by
pressing [#] key.
Option 6 refers to deactivating the audible tamper alarm, if the alarm source
partition is disarmed – the alarm is only signaled in the keypad.
Option 7 refers to limiting the number of triggered alarms to 3 per one zone at
time intervals shorter than 1 minute. If, when the partition is armed, the control
panel receives 3 violation messages concerning one zone in time intervals shorter
than 1 minute, it will generate an alarm after each violation, all subsequent
violations of that zone being ignored, unless at least one minute elapses since the
last violation.
If this option is inactive, violation of a zone when the partition is armed will
generate an alarm, provided the keypad is not already signaling a previous alarm.
If the keypad is already signaling an alarm, violation of the zone will not cause
a new alarm.
FS-132 - programming clock correction (DEC)
As time measurement by the control panel internal clock may differ from the real
value, provision has been made for making a daily time correction. The function
makes it possible to correct the time measurement by ±19 seconds within 24
hours. For programming the time correction, use the function FS132 to enter the
value of daily time shift of internal clock:
00 no correction
01 +1 second
02 +2 seconds
...
19 +19 seconds
81 -1 second
82 -2 seconds
...
99 -19 seconds
EXAMPLE:
program the time correction by -12 seconds
[1][3][2] [#] - call the function
[9][2] [#] - enter the correction value (minus 12 seconds)
FS-133 - programming the time of test transmission to the monitoring station
(DEC)
The alarm system makes it possible to set a maximum time interval between
transmissions of event codes. If the preset time interval elapses after the last
monitored event, the control panel will send the test transmission code. The
function parameter (three two-digit numbers meaning days, hours and minutes)
determines the time counted from the last transmission. If any event, the code of