Installation guide

Section 4 - Programming – Service Functions 61
The code 4 is recorded in the event log when lack of communication with
the station lasted so long that all the memory intended for the events (255 in
all) has been filled up and the oldest events have been erased.
FS-83 - programming system event assignment to station 1 (BIT)
When the mode of notifying both stations is active, the events programmed with
the function FS-82 are sent to both stations, For the other system events
(programmed with the function FS-81), it is possible to determine, whether they
will be sent to station 1, to station 2, or to both of them. The function FS-83 selects
events to be sent to station 1.
Programming in the LED keypad is a two-stage process (similarly as in FS-73 to
FS-76). The LEDs 1 to 8 show the following events:
1 - AC loss
2 - AC restore
3 - Low battery
4 - Battery restore
5 - Output OUT1 trouble
6 - Output OUT1 restore
7 - Output OUT2 trouble
8 - Output OUT2 restore in the first stage
1 - Output OUT3 trouble
2 - Output OUT3 restore
3 - Printer trouble
4 - Printer restore
5 - Enter service mode
6 - Exit service mode
7 - Start DOWNLOADING
8 - Stop DOWNLOADING in the second stage
FS-84 - programming system event assignment to station 2 (BIT)
The function makes it possible to select system events sent to the station 2, when
the mode of reporting to both stations is active. The programming procedure is
identical as in FS-83.
FS-85 - programming test transmission time (DEC)
The control panel can send the test transmission every 24 hours. The function FS-
85 sets the hour and minute for sending the test code to the monitoring station.
The programming consists in entering two two-digit numbers: hours (00 to 23) and
minutes (00 to 59). After confirmation of the minutes, the panel quits the function.
Entering 99:99 disables the test transmission function.
EXAMPLE:
programming the test code to be sent at 1:45
[8][5] [#] - call the function
[0][1] [#] - enter the hour for message sending
[4][5] [#] - enter the minutes and exit the function
FS-86 - programming the „AC loss” report delay (DEC)
The function defines the time from the mains supply loss after which the panel will
send an „AC loss” message to the monitoring station. The delay time is
programmed in minutes, within the range from 01 to 99 minutes. The mains
supply loss is signaled instantly in keypads and on the AC loss indicator outputs.
Functions Programming Dialer
FS-87 - programming telephone number 1 (HEX)