Installation guide
52 Functions Programming Output Parameters
EXAMPLE:
programming the OUT1 output for the BURGLARY/FIRE ALARM type operation, for
5 minutes, with polarity 0V in active state
[3][1] [#] - call the function. When it is activated, the LEDs will show current output type (LEDs 1
to 4 and 5 to 8 will show two digits in binary form). The blinking LED 12 signals the
output type being programmed.
[0][2] [#] - enter and confirm the output number (the LED 12 starts blinking - operation time
programming)
[0][5] [#] - program and confirm the time (LEDs 11 and 12 start blinking - proceed to programming
the output option)
[6] - LED 6 goes on - the βtime in minutesβ option is activated
[8] [#] - LED 8 goes off - set the "polarity" = 0V and exit the function.
FS-32 - programming list of zones OUT1 (BIT)
The function is used to program the output controlling zones. The selection of
zones limits the output operation only to reaction to violation of those zones.
The zone selection should only be used when it is necessary to have
separate signaling for events from a specific zone or a group of zones.
In no list of zones is indicated, the control panel will assume by default that the
output reacts to events from any zone β for example, the BURGLARY alarm type
output will signal alarms for each alarm zone in the control panel. Of course, the
zone function (reaction type) is taken into consideration, e.g. the alarm signaling
output will not react to a change of state of the arming zone.
Programming the list of zones makes the control panel to skip the
programmed selection of zones when defining which zones are to activate the
output.
For the outputs reacting to keypad events, the list of partitions is taken into
consideration, while the list of zones is irrelevant (e.g. the 3 wrong codes alarm
signaling).
The FS-32 function is used to assign zones to the OUT1 output. The programming
procedure is identical as in the functions FS8 β FS19.
The programming in the LED keypad consists in lighting up the LEDs which
correspond to the zones (first select the zones 1 to 8 - the LED 12 is blinking, then
9 to 16 - the LED 11 is blinking). Consecutive steps must be confirmed.
FS-33 - programming OUT2 output
The function defines the basic parameters associated with the OUT2 output. The
programming procedure is same as for the FS-31.
FS-34 - programming list of zones OUT2 (BIT)
The function programs the list of zones associated with the OUT2 output. The
programming procedure is same as for the FS-32.
FS-35 - programming OUT3 output
The function defines the basic parameters associated with the OUT3 output. The
programming procedure is same as for the FS-31.
FS-36 - programming list of zones OUT3 (BIT)
The function programs the list of zones associated with the OUT3 output. The
programming procedure is same as for the FS-32.
FS-37 - programming OUT4 output
The function defines the basic parameters associated with the OUT4 output. The
programming procedure is same as for the FS-31.