Installation guide
Section 4 - Programming – Service Functions 51
30 - TIMER
31 - AUDIBLE ALARM STATUS
32 - FULL ARM STATUS
33 - ARM/DISARM/CLEAR ALARM
34 - KEYPAD ALARM BUZZER
35 - POWER SUPPLY IN ARMED MODE
36 - STATUS LED
37 - STATUS RELAY
38 - ZONE TROUBLE
39 - NO GUARD CODE
40 - SERVICE MODE STATUS
41 - LOW BATTERY INDICATOR
Output operation time (the LED 11 is blinking) is defined in the second step by
entering a number from 00 to 99 (as in other DEC functions). A corresponding
option defines whether the operation time has been given in seconds or minutes.
The third parameter (the LEDs 11 and 12 are blinking) is a set of eight options
to define i.a. the output assignment to partitions, and other details of the output
operation. The options are programmed in much the same way as the other BIT
functions.
OUTPUT OPTIONS:
No. LCD LED
Option
ON
output belongs to
partition 1
1
OFF
output not assigned to partition 1
ON
output belongs to
partition 2
2
OFF
output not assigned to partition 2
ON
output belongs to
partition 3
3
OFF
output not assigned to partition 3
ON
output belongs to
partition 4
4
OFF
output not assigned to partition 4
ON
pulsating signal
5
OFF
steady signal
ON
operation time in
minutes
6
OFF
operation time in
seconds
ON
LATCH type output –
signaling until cleared
(operation time irrelevant)
7
OFF
output operates periodically
ON
polarity +12V
when the output is active
8
OFF
polarity 0V
when the output is active
After confirmation of the option, the function is quitted.
NOTE: The option of output assignment to a partition is to be used, when
separate signaling devices have to be assigned to individual partitions. If not
assigned to a partition, the alarm output will signal every alarm.