Installation guide
42 Functions Programming Basic Parameters
FS-6 - programming entry delay, exit delay , and alarm time (DEC)
The settings refer to the global times and are valid for the entries and exits to
which no individual times are assigned. The exit delay time is common for all
partitions. The alarm time programmed in this function refers also to the keypad
alarm signaling.
NOTE: The alarm time set with the function FS-6 defines also the zone alarms
cut-off time - when the alarm is on, the subsequent zone violations will not
trigger consecutive alarms until the cut-off time has elapsed.
Programming the times is carried out in the following order:
entry delay (from 01 to 99 seconds) - in LED keypad, the LED 12 is blinking
exit delay (from 01 to 99 seconds) - in LED keypad, the LED 11 is blinking
alarm time (from 01 to 99 seconds) - in LED keypad, the LEDs 11,12 are
blinking.
EXAMPLE (for LED keypad):
programming the times: T
WE
= 30 s, T
WY
- 60 s, T
AL
- 90 s
[6] [#] - call the required function
[3][0] [#] - enter the entry delay time (two digits)
[6][0] [#] - enter the exit delay time (two digits)
[9][0] [#] - enter the alarm time; after acknowledging the last time, the control panel automatically
exits the function.
When programming from the LCD keypad, pressing the [#] key confirms all the
three times entered.
FS-7 - programming the counting line counters (DEC)
The control panel is equipped with three independent violation counters which can
be associated with any zones. Violation of these zones will trigger alarm after the
programmed number of violations is exceeded in the respective zone counter.
Each counter can sum up violations of one or several zones defined as the
counting ones (e.g. the counter 1 can count violations of zone 2, the counter 2 -
violations of zones 4, 5, 6).
- Number „0” programmed – no alarm.
- Number „1” programmed – alarm after second violation.
- Number „2” or higher programmed – alarm after the number of violations
equal to the programmed number.
Three counter values are programmed, from 01 to 07, in the following order:
counter 1, counter 2, counter 3. If no counting zones are provided in the panel, the
programmed values are irrelevant.
Time gates corresponding to the counters are programmed in FS-123.
EXAMPLE (for LED keypad):
programming the counters: the 1
st
- 2 violations, the 2
nd
- 5 violations, the 3
rd
- not used
[7] [#] - call the function
[0][2] [#] - program the first counter (the lower LED B is blinking)
[0][5] [#] - program the second counter (the lower LED A is blinking)
[*] - exit the function - programming of the third counter is omitted
In case of programming three counters, the function is automatically exited after
the third counter has been programmed.
Functions programming assignment
FS-8 - programming partition 1 zones (BIT)
FS-9 - programming partition 2 zones (BIT)
FS-10 - programming partition 3 zones (BIT)