Installation guide

Section 3 - Activation of Selected Functions 31
alarm system identifier (facility number - one or more for detailed reporting
from a big system )
list of event codes
In order to start monitoring, the following items should be programmed:
FS-43 – monitoring station telephone number - if there are two numbers or
two stations, the other number should also be programmed in FS-44.
FS-45, FS-46 – station transmission formats - in case of a multi-format
station, select format which is as fast as possible (e.g. Ademco Express or
Radionics 2300 with parity).
FS-47 – monitoring options.
FS-48 to FS-59 – monitoring stations identifiers, an identifier should have 3
or 4 non-zero characters (characters from “1” to “F”, “0” - no character), some
stations use identifiers composed from digits from 0 to 9 - then character “A” is
to be programmed instead of digit “0” (e.g. “A1A2” instead of “0102”.
At least three identifiers should be programmed (can be identical):
- zone identifier,
- partition identifier,
- system event identifier.
FS-60 to 66 & FS-69 to 72, FS-81,82,126 – event codes according to the list
from the monitoring station operator, the codes can be one-digit (the other
character being 0) or two-digit - as required by the station, the codes with
inappropriate length may block communication with the station.
If reporting with event sorting to both stations has been selected in the
options, events assignment should be programmed in the functions FS-67, 68,
73 to 80, 83, 84.
FS-5 - activate the option in “MONITORING” after the above items have
been programmed.
Typical problems with starting the monitoring:
Control panel takes no attempts to call – not all of the above mentioned
items have been programmed – the control panel will not call the monitoring
station if the programmed data do not allow sending a correct transmission to
the station because of e.g. missing telephone number, identifier being shorter
than 3 non-zero characters, missing event code, etc.
Problems with dialing – no dial tone or a non-standard dial tone from the
telephone exchange – find out the cause of missing signal or disable the dial
tone test option in FS-5 if the signal is non-standard.
Control panel sends no codes when connected to the station - wrongly
selected format or low quality of telephone connection (the panel does
not “understand” the station dial tone);
Station does not receive or acknowledge the codes sent by the panel
- wrongly selected format, inadequate identifier length (3 characters, while the
station requires 4), inadequate event code length (1 character, while the station
requires 2) or low quality of telephone connection.
Control panel does not send codes of some events, despite of the codes
being properly entered - identifier of the particular group of events is missing,
e.g., if the partition 1 identifier is missing, no reports on this partition arming /
disarming will be sent.
Control panel automatically changes the option „transmission to Station
1 or to Station 2” into transmission to one station only - if with this
monitoring option selected the number of identifiers for Station 1 and Station 2
is different (there are codes which have an identifier for one station, but not for