Installation guide

28 Installation Guide CA-10 plus SATEL
control panel will not start on connecting the battery alone (without the
mains power connected), however, it will keep on working in case of the
230V AC voltage trouble, provided it was already started.
2. Switch on the 230V AC mains supply – the control panel start follows.
Connection of the power supplies in the prescribed order will permit correct
functioning of the power supply unit and the control panel electronic safety
devices, thus avoiding damage to the security system elements caused by
possible installation faults.
NOTE! Should it be necessary to completely disconnect the control panel
power supply (the mains and the battery), re-connection of the power
supply is to be performed in the above mentioned order (the battery
first, then the 230V alternating voltage).
Caution !
As the control panel has no isolating switch to disconnect the mains supply, it is
important that the owner or the user of the security system be informed on how
the system is to be disconnected from the mains (e.g. by indicating the fuse which
protects the control panel supply circuit).
Starting the Control Panel
When all electrical connections are made and checked for correctness, you can
proceed to starting the system. It is recommended to begin the work with the control
panel with no signaling devices connected. These can be connected after
programming parameters of the realized alarm system is completed.
If the control panel operates with one keypad, having a default address (jumpers on
pins „A” and „D”), then, after the power is switched on, the keypad will report
readiness for work with four short beeps followed by a long one.
Upon entering the default service code [1][2][3][4][5] and confirming it with the [#]
key, the control panel will enter the service mode. The ALARM and ARMED LEDs
(PARTITION in the LCD keypad) will be blinking alternately. Now, you can proceed
to programming the control panel.
If there are more than one keypad connected in the system and the default address
of the first keypad (CLK1) has been changed, or there is a zone expander installed,
or, for whatever reason, the panel does not „see” the keypad when the power is on,
and does not respond to the keystrokes (access code entry), or keeps on alarming, it
is necessary to carry out the procedure of hardware access to the service mode. If
this is the case, you must carry out programming of the keypad / expander
addresses before the normal operating mode is restored. If you fail to do so, the
control panel will start alarming right after the power-up because it has detected the
keypad tampering.
If this is the case, switch off the power supply (mains and battery) and:
1. Check the keypad address jumpers and anti-tampering contacts for correct
settings.
2. Put a jumper on the control panel RESET pins (J19).
3. Switch the power supply on. After the keypad beep, remove the jumper from
the RESET pins (J19). The operation will activate the service mode in partition 1
keypad. This will be signaled by the keypads with four short and one long beeps.
4. Call the service function FS-124. The function automatically reads the keypad
address and prepares the control panel for work in a new configuration.