Installation guide

Section 1 - Description of the Control Panel 17
waiting for a call from the computer for four hours even when the functions of
automatically answering the computer call are disabled. When the communication is
ended with the “end” command instead of “suspend”, the information on ending the
communication is entered into the event log and sent to the monitoring station after
four hours.
As the control panel is only accessible to the service, a number of protective devices
is provided to prevent hacking of the system and change of any data by unauthorized
persons. All the data exchanges are authorized by changing the access codes and
the data are encoded.
The DOWNLOADING can be particularly useful to installation firms engaged in
servicing many alarm systems. Then the user suggested inspections and
modifications of software will not necessarily require troublesome and costly traveling
- they will be carried out with a computer via the telephone line. Such a method of
customer service and technical control of customer systems will allow creation of
alarm equipment services at an advanced and professional level.
INSTALLATION OF THE CONTROL PANEL
Description of Control Panel Main Board
The control panel main board contains electronic components sensitive to electric
charges. Prior to installation, these charges must be removed. During installation,
avoid touching any elements on the control panel main board.
BOARD TERMINALS:
AC - module power supply inputs (17...24V AC)
Z1 to Z8 - zone inputs
OUT1 to OUT4 - programmable outputs (current-carrying capacity 2.2A)
OUT5 to OUT6 - programmable outputs (current-carrying capacity 50mA)
+KPD - keypad power supply output
+12V - power supply outputs
COM - ground
DATA - common terminal of keypads
CLK1 to CLK4 - individual terminals of separate partition keypads
- protective terminal - ground (connect to protective circuit only)
TIP, RING - terminals of outside telephone line
T-1, R-1 - terminals of extension telephone line (telephone set)
J22 - connector for OUT5 & OUT6 output, power supply and ground
lead-outs
J18 - connector for SM-2 voice synthesizer