Installation guide

8 Installation Guide CA-10 plus SATEL
Outputs
The CA-10 plus is equipped with 6 programmable outputs: 4 high-current and 2 low-
current ones.
The OUT1, OUT2, OUT3 and OUT4 outputs are protected by special electronic
fuses with current limiters set at 2.2A. The panel monitors presence of voltage,
overload, and signals trouble conditions at these outputs. 2.2k resistors must be
connected in parallel to these outputs. The above outputs supply the load with +12V
voltage.
The OUT5, OUT6 (low-current, up to 50mA) outputs control ground of the load.
All outputs are equipped with protective devices for inductive loads and pulse
interference.
Designation of the outputs can be adapted for the needs of the alarm system
controlled by the panel. Though individual outputs differ by their design, each of
them can perform one of the following functions:
1 - BURGLARY
- the output starts on detecting a burglary alarm by the control panel. The
alarm is triggered by armed zones, zone anti-tampering circuits, keypad tamper
detectors, and by the user (through the ALARM PANIC function). If the zones to
which the output is to react are defined, the zone alarms will be limited to those
included in the „list of outputs” (the other alarms will be effected irrespective of the
source). It is also possible to indicate (in the output options) the partition the output
is associated with. If this is the case, the zone alarms will be limited to those from
the zones belonging to the partition indicated. When the "list of outputs" is empty
and no partitions are indicated, the output reacts to all alarms (except for the fire
alarms).
The output can remain active for a specified time (from 01 to 99 seconds or from
01 to 99 minutes) or until the alarm is cleared by the user. During its operation, it
can every second change its state (pulsate).
2 - FIRE/BURGLARY -
the output starts on detecting by the control panel of a burglary
alarm (continuous signal) and/or a fire alarm (intermittent signal). The output
operation can be limited to the indicated "list of outputs" or a specific partition
(identically as for the
01
output type). The output can remain active for a specified
time (from 01 to 99 seconds or from 01 to 99 minutes) or until the alarm is cleared
by the user.
3 - FIRE
- the output starts when the control panel detects a fire alarm. Such an alarm is
triggered by fire zones or the user (through the ALARM FIRE function). The output
operation can be limited to the specified "list of outputs" or particular partitions
(identically as for the
01
output type), indication of any zones other than the fire
ones having no sense, as they would not generate a fire alarm. The output can
remain active for a specified time (from 01 to 99 seconds or from 01 to 99 minutes)
or until the alarm is cleared by the user. During operation, it can every second
change its state (pulsate).
4 - KEYPAD ALARMS
- the output starts on detecting any keypad alarm (FIRE, PANIC,
AUX., keypad tamper alarms). The output operation can be limited to the alarms
from specified partitions. The output can remain active for a specified time (from 01
to 99 seconds or from 01 to 99 minutes) or until the alarm is cleared by the user.
During its operation, it can every second change its state (pulsate).
5 - KEYPAD FIRE ALARM
- the output starts on triggering the fire alarm by the user
(with the FIRE ALARM function). The output operation can be limited to the alarms
from specified partitions. The output can remain active for a specified time (from 01
to 99 seconds or from 01 to 99 minutes) or until the alarm is cleared by the user.
During operation, it can every second change its state (pulsate).
6 - KEYPAD PANIC ALARM
- the output starts on triggering the PANIC alarm by the
user. The output operation can be limited to the alarms from specified partitions.
The output can remain active for a specified time (from 01 to 99 seconds or from
01 to 99 minutes) or until the alarm is cleared by the user. During operation, it can
every second change its state (pulsate).