User`s guide

Section 5 – Displaying and Using the Tuning Screens
5.2 Profit Optimizer’s DQP CV Optimizer Tuning Display
1/00 Profit Optimizer User's Guide 69
Honeywell Inc.
Table 5-1 Profit Optimizer CV Optimizer Tuning Functions
Use Profit Optimizer’s DQP CV Optimizer Tuning Screen for These Tasks . . .
Operator Engineer
There are no Operator tasks from this display
(default).
Setting the 1st and 2nd order coefficients that define the
economic objectives for the process.
Setting the desired CV resting value
Field Descriptions
Table 5-2 Profit Optimizer’s DQP CV Optimizer Tuning Display Understanding the Fields and
Using the Targets
Profit Optimizer’s DQP CV Optimizer Tuning – Field Descriptions and User Notes
Field
Description
Field Type Default Access
User Notes
APL
Read-Only No Access
The Profit Controller (RMPCT) application number
CV #
Read-Only No Access
The CV number within the Profit Controller (RMPCT)
Application.
CV Description
Target OPER
Description that characterizes the variable's function or
location.
Select the target to call the CV Detail
screen.
Linear Obj Coef
Target ENG
Linear objective coefficient.
Positive values drives CV to low limit
negative values drive CV to high limit
Quadratic Obj Coef
Target ENG
Quadratic objective coefficient.
Desired CV Value
Target ENG
Desired resting value for the CV during quadratic
optimization.
.
Soft Lo Limit
Read-Only No Access
Offset from the control low limit that defines a low limit
for optimization.
These values are used down in the Profit
Controller and are shown here for
information only.
Soft Hi Limit
Read-Only No Access
Offset from the control high limit that defines a high limit
for optimization.
These values are used down in the Profit
Controller and are shown here for
information only.