User`s guide

Section 4 – Displaying and Using the Detail Screens
4.3 Profit Optimizer’s DQP MV Detail Display
1/00 Profit Optimizer User's Guide 53
Honeywell Inc.
Table 5-3 Profit Optimizer’s DQP MV Detail Control Functions
Use the Profit Optimizer’s DQP MV Detail Screen for These Tasks . . .
Operator Engineer
Displaying the MV status and operating values.
Setting MV high and low limits.
Select [TAG] to see the Point Detail pages for the MV.
Select [DESTN] to see the Point Detail pages for the downstream
point Profit Optimizer is writing to.
Toggling RMPC and OPR modes for non critical MVs.
Displaying the MV predicted future and steady state values.
Displaying the current and predicted MV values.
Describing the MV.
Dropping MVs or using as feedforward control.
Setting critical or non critical MV control.
Setting MV ramp rates.
Setting maximum MV moves per execution.
Entering the desired MV resting value.
Setting MV economic objective functions.
Field Descriptions
Table 5-4 Profit Optimizer’s DQP MV Detail – Understanding the Fields and
Using the Targets
Profit Optimizer’s DQP MV Detail – Field Descriptions and User Notes
Field
Description
Field Type Default Access
User Notes
Tag
Target OPER
Tag name. The name of the RMPCT MV Interface
display point.
Select the target to call the Point Detail pages.
Desc
Target ENG
Description that characterizes the variable's function or
location.
To re-describe the variable, touch the target, type
the new description, press <ENTER>.
Destn
Target OPER
Destination point. The downstream MV (the downstream
controller) receiving the dot-SP or dot-OP control
instruction from Profit Optimizer.
Select the target to call the Point Detail pages for the
downstream point Profit Optimizer is writing to.
Tgt Value
Read-Only No Access
The value sent to the SP or OP of the MV at the current
execution.
Curr Value
Read-Only No Access
The value of the MV at the current execution.
Curr Move
Read-Only No Access
The size and direction of change made to the immediate
downstream controller at the last execution.
The change is made to the point parameter named
in [DESTN].