User`s guide
Section 2 – Application Selection and Optimizer Detail Displays
2.3 RMPCT DQP Detail Display
1/00 Profit Optimizer User's Guide 27
Honeywell Inc.
RMPCT DQP Detail Field Descriptions and User Notes
Field
Description
Field Type Default Access
User Notes
SYSTEM CONFIG
Targets
Target E
N
Displays the Profit Controller point and
Bridge DV point configuration screens.
Use the configuration screens for specifying and
describing Profit Controllers and BDVs. Select
SYSTEM CONFIG target for the variable.
Max Init Intrvls Reserved
Max Num Overlps
Target E
N
The number of allowable consecutive
missed optimizer executions, overruns.
A missed execution occurs when the Profit Optimizer
is waiting for other optimizers or other tasks to
complete. An overlap occurs when calculations (point
executions) from one optimizer execution period over
run into the next scheduled period.
Init Intrvals Reserved
# of Overlaps
Read-Only No Acce
s
Number of consecutive times calculations
have over run into the next scheduled
period.
When # of Overlaps = Max Num Overlaps, the
optimizer shuts down.
# BDV Inputs Bad
Target E
N
Number of consecutive times a bridge input
value can be bad before it is considered
BAD.
When critical BDV is set BAD, Profit Optimizer is
automatic set OFF.
# BDV Bad Re-Init
Target E
N
Number of consecutive times a bridge input
value can be bad before the bridge input
model is initialized.
This value is usually set greater than or equal to the #
BDV inputs bad value.
Read Model File
Target
E
• W INIT = Reads in the .YM model file
and initialize the bridge model/combined
constraints.
• W/O INIT = Reads in the .YM model file
without initializing the bridge
model/combined constraints.
• Use this option to read in a new model from a new
off-line design.
• You can set only one of the targets.
Read Spec File
Target
E
Reads in the .YS specification file when set.