Shutting Down / Reloading / Restarting the AM
1/00 Profit Optimizer User's Guide 113
Honeywell Inc.
Shutting Down / Reloading / Restarting the AM
Procedure
Table A-13 How to Shut Down the AM
Step Action Comments
1 From the Optimizer Bar, turn off all the
optimizers on the system.
Control sheds to configured Profit
Controllers (RMPCTs).
2 Checkpoint the AM.
3 Shut the AM down.
4Restart.
5 Display the optimizer main menu.
6 Select every optimizer you want on-line, and
turn the optimizer ON from the Optimizer Bar.
If you want to watch an optimizer first
before putting it in charge of your process,
use WARM, watch the process, then turn
ON.
Notes
ATTENTION
See “Inactivating the Optimizer Point” earlier in this section for important
reasons why you always turn a
Optimizer OFF before taking the optimizer
point off the process.