Section 7 – Displaying and Responding to Profit Optimizer Messages
7.4 Dictionary of Profit Optimizer Messages
96 Profit Optimizer User's Guide 1/00
Honeywell Inc.
Profit Optimizer
Messages
76 - 82
76
Message: Turning DQP off
Fatal Error
Meaning Suggested Response
The number of consecutive bad BDVs is greater than the
max limit, or some RMPCTs are inactive.
When all RMPCTs are active and BDVs are ok,
turn Profit Optimizer (DQP) back on.
77
Message: # of RMPCTs/BDVs in CDS mismatches model
Fatal Error
Meaning Suggested Response
Number of RMPCTs or number of bridged ouputs in CDS
mismatches the one in pool.
Check the off-line design and CDS.
78
Message: RMPCTs w/ BOuts must run as often as DQP
Fatal Error
Meaning Suggested Response
The Control Execution interval of RMPCTs w/BOuts must
be larger than DQP’s control execution interval
Check the Control execution interval of Profit
Controller (RMPCT) and Profit Optimizer (DQP)
79
Message: No. BOuts in Model file out of range
Fatal Error
Meaning Suggested Response
Number of bridged outputs in YM file is either less than 0
or greater than 50
Check the off-line design
80
Message: No. BIns in Model file out of range
Fatal Error
Meaning Suggested Response
Number of bridged inputs in RM file is either less than 0 or
greater than 150.
Check the off-line design
81
Message: Inconsistent no. of BIns and BOuts in YM
Fatal Error
Meaning Suggested Response
One of the numbers of BIns/BOuts is zero, the other on is
not.
Check the off-line design
82
Message: Number of CCs in YM out of range
Fatal Error
Meaning Suggested Response
Number of Combined Constraints in YM is either less than
zero, or greater than 100
Check the off-line design