User`s guide
Section 7 – Displaying and Responding to Profit Optimizer Messages
7.4 Dictionary of Profit Optimizer Messages
1/00 Profit Optimizer User's Guide 95
Honeywell Inc.
Profit Optimizer Messages
70 - 75
69
Message: Bridged DV interface point missing/inactive
Fatal Errors
Meaning Suggested Response
Bridged DV interface point missing/inactive, or could not
find BGD_CDS on bridge output point
Check Bridged DV point
70
Message: Error moving DIN_CDS or DMOD_CDS
Fatal Errors
Meaning Suggested Response
DIN_CDS or DMOD_CDS on RMPCT/DQP interface point
may have error
Check DIN_CDS and DMOD_CDS
71
Message: Profit Controller (RMPCT) has too few MVs or DVs for brg mdl
Fatal Errors
Meaning Suggested Response
Not enough room for current bridge models and combined
constrains.
Use the supported message to identify which
RMPCT has error, go through off-line design then
rebuild and reload Profit Optimizer (DQP)
72
Message: An RMPCT has too many BDVs
Fatal Errors
Meaning Suggested Response
Too many bridged outputs in a single Profit Controller
(RMPCT)
Reduce the number of bridged DVs in the off-line
design, then rebuild and reload Profit Optimizer
(DQP)
73
Message: # of RMPCTs/BDVs in file mismatches CDS
Fatal Errors
Meaning Suggested Response
The number of RMPCTs or bridged outputs in the YM file
doesn’t match CDS
Check the off-line design and CDS
74
Message: Specification file doesn’t match model
Fatal Errors
Meaning Suggested Response
Number of bridged outputs in the YS file doesn’t match the
number in the YM file.
Check the bridged DVs off-line design.
75
Message: Some crit RMPCTs not ON, turning Profit Optimizer (DQP) off
Fatal Error
Meaning Suggested Response
At least one critical Profit Controller (RMPCT) is not ON. When all Profit Controllers(RMPCTs) are ON,
Turn Profit Optimizer (DQP) back on.