User Guide
AXlink Wiring Considerations
4
AXlink Wiring Considerations
Liberty Cable & Wire Inc. cables
FIG. 3 shows a wiring diagram for AXlink cables manufactured by Liberty Cable & Wire Inc. The
PWR connection shown in the diagram is only used when supplying 12 VDC via the AXlink cable.
The PWR connection should not be used when a local power supply is connected directly to the
external AXlink device.
Belden 8102-compliant cables
Belden 8102-compliant cable contains two single twisted pairs (STP) of 24 AWG with a single
drain wire. The nominal capacitance between conductors is 12.5 pF/ft. Using Belden 8102-
compliant cable for AXlink data communication, the maximum overall cable distance between the
Central Controller and all external devices is 3,000 feet with no remote power.
FIG. 4 shows a wiring diagram for the AMX-approved Belden 8102 AXlink cable. The PWR
connection shown in the wiring diagram is only used when supplying 12 VDC via the AXlink
cable. The PWR connection should not be used when a local power supply is connected directly to
the external AXlink device.
Category 5-compliant cables
Category 5 cable contains four unshielded twisted pairs (UTP) of 24 AWG solid wire. The nominal
capacitance between conductors is 15.0 pF/ft. Using Category 5-compliant cable for AXlink data
communication, the maximum overall distance between the Central Controller and all external
devices is 1,000 feet. If the installation site's wiring conforms to EIA/TIA 568 Category 3
standards, AXlink data communication will function properly. However, power (PWR) cannot be
used with EIA/TIA 568-Category 3 standard cable because of connector types and punch blocks.
FIG. 5 shows a wiring diagram for Category 5-compliant cable used for AXlink data
communication. The PWR connection shown in the wiring diagram is only used when supplying 12
VDC via the AXlink cable. The PWR connection should not be used for EIA/TIA 568 cable
installations.
FIG. 3 Standard AXlink power/data wiring diagram
FIG. 4 Belden 8102 wiring diagram