Specifications
Errors Ver. 0002 B - 7
211 Internal Error.
Get in touch with Fagor Automation.
212 Overcurrent.
- Too much current at the Drive module. Drive malfunction.
Reset the error, the parameter settings might be wrong and they cause overcurrent.
213 Undervoltage at the IGBT drive.
- Low supply voltage is detected in the IGBT attack circuitry in the Drive module. Possible failure on the
drive of the IGBT or the IGBT itself.
Reset the error, and if this goes on, get in touch with Fagor Automation.
214 Short-circuit.
- Short-circuit at the Drive Module.
Reset the error. If it persists, the power cables might be connected in the wrong order or that they touch
each other causing the short-circuit. The parameters might be wrong or there is a Drive malfunction.
Contact Fagor Automation
215 Overvoltage at the Power Bus of the drive (hard).
- The hardware of the drive module has detected excessive voltage at the Power bus. Internal Ballast
connection jumper missing (see power connectors). Or, when using an external Ballast, it is not
connected properly. The Ballast resistor is burned out.
Power it down and check for proper Ballast circuit connection.
See errors 304 and 306.
250 - 253 Homing error.
Get in touch with Fagor Automation.
300 Overtemperature at the heatsink of the Power Supply, or Compact module.
301 Overtemperature at the Ballast of the Power Supply, or Compact module.
- Temperature of the heatsink or of the Ballast circuit of the Power Supply module too high.
Stop the system for a few minutes and reduce the level of effort required of this module.
302 Short-circuit at the Ballast of the Power Supply module.
Get in touch with Fagor Automation.
303 Supply voltage of the Ballast circuit driver out of range.
Get in touch with Fagor Automation.
304 Overvoltage at the power bus of the PS.
- The power supply has detected excessive voltage at the power bus. The internal Ballast may be
disconnected (see Power Supply Module) or, when using an external Ballast, it is not connected.
Turn the power off and check that the lines are OK.
See errors 215 and 306.