Specifications

AP - 18 Applications Ver. 0002
Operation with the Strobe always active:
GV24 "Strobe" will stay active if it is not assigned to a digital input.
This way the change of sets is handled directly without control signals, with GV32-30.
in order to avoid possible disturbances or rebounds on those electrical signals, they
should maintain their new values for at least 20 milliseconds.
The drawing below is an example.
Remarks:
The active set may be changed while the motor is running. If the motor is turning faster
than the limit established by the new parameter set, the speed will decrease
automatically until the value of such limit is reached and only then, the new parameter set
will become effective. The ramp used to make this change of speed will be the one
determined by the previous set.
t
IP12=GV31
24 V
0 V
24 V
0 V
24 V
0 V
GV21 ActualParameterSet
t
t
t
t
023
1
0
GV23 SetChan
g
eAck
1
0
1
0
1
0
IP13=GV30
IP10=GV24
pin3-5 X6
pin4-5 X6
pin1-5 X6
Strobe
Acknowled
g
e
20 ms
GP4=4
t
IP12=GV31
24 V
0 V
24 V
0 V
t
t
t
013
1
0
GV24=1
unassigned
1
0
1
0
IP13=GV30
pin3-5 X6
pin4-5 X6
20 ms 20 ms< 20 ms
Acknowledge
GV23 SetChangeAck
GV21 ActualParameterSet
>100 ms
GP4=4