Specifications

SSU - 12 Velocity Drive Setup Ver. 0002
SV8 -F01612-
SV7 -F01613-
Emergency Ramp (example):
Speed
(rpm)
SP65
0
1500
0.1
SP65=1500/0.1/9.5=
157
8 rad/seg
2
Time
(sec)
SpeedEnable Function
Halt Function
Error Stop
OR
OR
SP70=1
SV8 -F01612-
SV7 -F01613-
Limit set by
SP10 -S00091-
=1900 rpm
Ramps (example):
Time
(sec)
Speed
(rpm)
SP63
SP61
SP60
SP64
SP62
Time
Speed
1750
500
0
1000
SP60=500/0.3/9.5=175
rad/seg
2
SP61=500 rpm
SP62=750/0.1/9.5=790
rad/seg
2
SP63=1750 rpm
SP64=150
rad/seg
2
(eg)
SP100=1
SP80=0
00.30.4
SP60 -S00138- SP61 -F01605-
SP62 -F01606- SP63 -F01607-
SP64 -F01608-
SSU.5.3.1 EMERGENCY ACCELERATION LIMIT
To filter the velocity command in an emergency stop, set SP70 -F01610- to "1".
An emergency stop is the one requested by activating the Halt function, by deactivating the
SpeedEnable, or the one due a Drive malfunction.
SSU.5.3.2 RAMP GENERATION
For this type of velocity command filter, set SP80 -S00349- = 0 and SP100 -F01611- = 1
The action of this Ramp Generator is divided into three velocity sections.
In each one of them, the acceleration can be limited to a different value.
From 0 rpm to SP61 Acceleration limited to SP60.
From SP61 to SP63 Acceleration limited to SP62.
And from SP63 on Acceleration limited to SP64.