Specifications
Installation Ver. 0002 IN - 11
IN.3.1.5 SECTION OF THE CABLES FOR MAINS CONNECTION.
The table on the right gathers the regulation applicable to
typical installations of Drive Systems.
Determines the maximum current in continuous duty cycle,
admitted by three-phase conductors in PVC hoses and
installed on the machines through conduits and channels.
The ambient temperature considered is 40 °C (94 °F).
At any rate, the section of the mains connection cables
must be equal to or greater than that of the cables used to
connect any motor.
To determine the cables needed to connect the Power Supply to Mains, proceed as
indicated in the DS chapter.
This is the cable selection offered by Fagor:
Section
(mm
2
)
Max Current
(Amp RMS)
1.5 12.2
2.5 16.5
423
629
10 40
16 53
25 67
35 83
Reference
number of cables x
section (mm
2
)
MPC - 4 x 1.5
MPC - 4 x 2.5
MPC - 4 x 4
MPC - 4 x 6
MPC - 4 x 10
MPC - 4 x 16
MPC - 4 x 1.5 + (2 x 1)
MPC - 4 x 2.5 + (2 x 1)
MPC - 4 x 4 + (2 x 1)
MPC - 4 x 6 + (2 x 1)
MPC - 4 x 10 + (2 x 1)
MPC - 4 x 16 + (2 x 1.5)
MPC - 4 x 25 + (2 x 1)
MPC - 4 x 35 + (2 x 1)