Specifications

Installation Ver. 0002 IN - 3
Climate conditions:
Watch that temperature in the electrical cabinet is always kept under 55°C (131°F). Never
install the Servo-Drive System beside a heat source.
The modules themselves generate heat. The following table shows the power dissipated by
each one of them. These are data to be borne in mind when deciding whether the electrical
cabinet needs external cooling or not.
External Ballast resistors RM-15 and ER should be mounted outside the electrical cabinet
because they are power dissipating elements which generate a lot of heat. They must be
installed away from splashes of water, coolant, metal chips, etc.
When applying external cooling to the system, make sure that water
condensation does not fall on the equipment.
(*) It depends on how often the protection
Ballast circuit is activated.
Module Dissipated Module Dissipated
power power
PS-25A 160 W APS 24 60 W
PS-65A 275 W CM-60 0 W
PS-25B 180 W RM-15 (*)
XPS-25 180 W ER (*)
XPS-65 350 W
ACD 1.08 92 W
AXD 1.08 65 W ACD 1.15 172 W
AXD 1.15 110 W ACD 1.25 220 W
AXD 1.25 180 W ACD 2.50 415 W
AXD 1.35 208 W ACD 2.75 575 W
AXD 2.50 335 W SCD 1.08 98 W
AXD 2.75 430 W SCD 1.15 173 W
AXD 3.100 680 W SCD 1.25 238 W
AXD 3.150 1200 W SCD 2.50 485 W
SPD 1.08 70 W SCD 2.75 677 W
SPD 1.15 135 W
SPD 1.25 200 W EMK 3040 30 W
SPD 1.35 296 W EMK 3120 45 W
SPD 2.50 385 W
SPD 2.75 570 W
SPD 3.100 830 W
SPD 3.150 1260 W