User Guide
Pre-Installation
4
AXC-TEMP Temperature Control Card and RTS1 Room Temperature Sensor
4. Hold the card by the tab end and slide the card into the frame. Make sure the card is correctly
positioned in the guide slot.
5. Gently push the card in until it is firmly seated in the card connector slot. It is not necessary to
disconnect the power to the CardFrame when installing the card.
Calibrating POTs
Use the four calibration potentiometers (POTs), marked CH 1 - CH 4, to adjust the respective RTS1
units 1 - 4. The default setting for each POT pointer is 0°. The table below describes the POT
calibration for CH 1 - CH 4.
Connecting Multiple RTS1s
FIG. 5 shows the pinout for the AXC-TEMP when connecting multiple RTS1s.
Calibration POTs CH1 - CH4
POTs Description
R1 Offsets input CHAN1 by -4 to +4 degrees
R8 Offsets input CHAN 2 by -4 to +4 degrees
R2 Offsets input CHAN 3 by -4 to +4 degrees
R9 Offsets input CHAN 4 by -4 to +4 degrees
R33 Stops Adj for input CHAN 1 (for RTS2 only)
R34 Stops Adj for input CHAN 2 (for RTS2 only)
R35 Stops Adj for input CHAN 3 (for RTS2 only)
R36 Stops Adj for input CHAN 4 (for RTS2 only)
FIG. 5 AXC-TEMP pinout for multiple RTS1s
PIN 1
PIN 16
IN3
IN4
GND
IN1
PWR
PWR
GND
IN2
GND
GND
PWR
PWR
TO RTS1 #1
TO RTS1 #2
TO RTS1 #3
TO RTS1 #4