instruction manual AXC-TEMP Temperature Control Card and RTS-1 Room Temperature Sensor Axcess Control Cards
Limited Warranty and Disclaimer AMX Corporation warrants its products to be free from defects in material and workmanship under normal use for a period of three years from date of purchase from AMX Corporation, with the following exceptions. Electroluminescent and LCD control panels are warranted for a period of three years, except for the display and touch overlay components which are warranted for a period of one year.
Table of Contents Table of Contents Product Information .................................................................................................1 Features ............................................................................................................................ 1 Pre-Installation ..........................................................................................................3 Setting Fahrenheit or Celsius ................................................................
Table of Contents ii AXC-TEMP Temperature Control Card and RTS1 Room Temperature Sensor
Product Information Product Information The AXC-TEMP Temperature Control card (FIG. 1) provides control and power for the RTS1 Room Temperature Sensor (FIG. 2). The RTS1 provides precision temperature sensing for the AXT-TEMP. FIG. 1 AXC-TEMP FIG. 2 RTS1 Features The AXC-TEMP features include: ! Standard Axcess CardFrame slot size ! Settings for Fahrenheit or Celsius operation ! Control and power for up to four independent RTS1 units ! Measurement accuracy of +/- 2°F (+/- 1.
Product Information The table below lists the specifications for the AXC-TEMP and RTS1. Specifications AXC-TEMP Input voltage +12 to 18 VDC Current Draw 40 mA (using four RTS1s = 75 mA) Temperature range 0.0 ° F to +250 ° F (0.0 ° C to +106.9 ° C) Accuracy +/-2 ° F (+/-1.1 ° C) Resolution 10-bit (1024 steps over range) RTS1 2 Weight 3.2 oz. (91 grams) Dimensions 4.5" x 2.
Pre-Installation Pre-Installation Before installing the AXT-TEMP and RTS1, you must properly set jumpers and potentiometers (POTs). Setting Fahrenheit or Celsius Set the Fahrenheit or Celsius feature by manually selecting each jumper (JP1- JP4) or by manually selecting the RAW A/D OUTPUT jumper on the card. FIG. 3 shows the location of the jumpers and POTs. The RAW A/D OUTPUT jumper overrides jumpers JP1 - JP4. Jumpers JP5 - JP8 Channels 1 - 4 Jumpers JP1 - JP4 and JP13 (RAW) Jumpers JP9 - JP12 FIG.
Pre-Installation 4. Hold the card by the tab end and slide the card into the frame. Make sure the card is correctly positioned in the guide slot. 5. Gently push the card in until it is firmly seated in the card connector slot. It is not necessary to disconnect the power to the CardFrame when installing the card. Calibrating POTs Use the four calibration potentiometers (POTs), marked CH 1 - CH 4, to adjust the respective RTS1 units 1 - 4. The default setting for each POT pointer is 0°.
Pre-Installation RTS1 Preparation To install the RTS1 units: 1. Wire RTS1 units 1 - 4. Refer to Wiring the RTS1 for additional information. 2. Check the temperature. ! If the panel has a display, check the temperature readings on the system Wiring control panel. The temperature readings will change when the room temperature changes by a half degree. ! If the panel does not have a display, check the variables in Axcess. Wiring the RTS1 Use Belden 8723 or equivalent cable.
Pre-Installation Axcess CardFrame AXC-TEMP Ground Black 1 Drain Green 2 Input White 3 Power Red Belden 8723, or equivalent (Twisted Pair) Black Ground Drain Green White Output RTS1 Unit 1 Red Power 4 6 Ground Black Drain Green Input White 7 Power Red 5 Belden 8723, or equivalent (Twisted Pair) Black Ground Drain Green White Output RTS1 Unit 2 Red Power 8 10 Ground Black Drain Green Input White 11 Power Red 9 Belden 8723, or equivalent (Twisted Pair) Black Ground Drain Green White Ou
Pre-Installation Testing the RTS1 Touch the sensor at the bottom each RTS1 unit for a few seconds. The temperature on the display panel should change. If the temperature does not change: 1. Check the wiring to each RTS1 unit that did not display a temperature change. 2. Verify the AXC-TEMP card is properly seated in the CardFrame. Repeat the steps provided in the RTS1 Calibration section on page 6, if required.
Pre-Installation 8 AXC-TEMP Temperature Control Card and RTS1 Room Temperature Sensor
Programming Programming This section provides the Axcess programming commands for the AXC-TEMP and RTS1. ! The TEMP_LEVEL variable receives data from the TEMP card (Device 16), inputs 1 - 4. ! The data is in three-digit numbers (986 = 98.6 degrees). The SEND_STRING command to the Mini-LCD Panel converts the number to print with a decimal point. ! The 12 clears the LCD screen.
ARGENTINA • AUSTRALIA • BELGIUM • BRAZIL • CANADA • CHINA • ENGLAND • FRANCE • GERMANY • GREECE • HONG KONG • INDIA • INDONESIA • ITALY • JAPAN LEBANON • MALAYSIA • MEXICO • NETHERLANDS • NEW ZEALAND • PHILIPPINES • PORTUGAL • RUSSIA • SINGAPORE • SPAIN • SWITZERLAND • THAILAND • TURKEY • USA ATLANTA • BOSTON • CHICAGO • CLEVELAND • DALLAS • DENVER • INDIANAPOLIS • LOS ANGELES • MINNEAPOLIS • PHILADELPHIA • PHOENIX • PORTLAND • SPOKANE • TAMPA 3000 RESEARCH DRIVE, RICHARDSON, TX 75082 USA • 800.222.