Specifications
406 US SALES AND SUPPORT 800.222.0193 • INTERNATIONAL SALES AND SUPPORT +1.469.624.7400 • www.amx.com
© January 2013 AMX. All rights reserved. AMX does not assume responsibility for any errors or omissions.
nXa-UPs1500 control system accessories
SPECIFICATIONS
DIMENSIONS (HWD)
•37/16”x175/16”x19”(8.8cmx44cmx48.2cm)
•RU:2
WEIGHT
70.3lbs(31.9kg)
INPUT
•VoltageWindow(DIPSwitchselectable):
-120Vversion(FG678-15):110/115/120VAC+35%–-32%
-240Vversion(FG678-20):220/230/240VAC+35%–-32%
•Frequency:45–65Hz(50/60Hzauto-sensing)
OUTPUT
•VoltageWindow(ACMode):
-120Vversion(FG678-15):110/115/120VAC+8%–-12%
-240Vversion(FG678-20):220/230/240VAC+8%–-12%
•VoltageWindow(INVMode):
-120Vversion(FG678-15):110/115/120VAC+/-5%
-240Vversion(FG678-20):220/230/240VAC+/-5%
•MaxOutputCurrent:
-120V:14A(continuous)
-240V:7A(continuous)
•Capacity(VA/W):1500/900
•WaveForm:Puresinewave
•Frequency:50Hz/60Hz+/-0.1Hz
•TransferTime:2mstypical
•Autonomy:>8min.
•DCStart:Yes
BATTERY
•Type:12V,sealedleadacidmaintenance-free
•Capacity:9AH
•Quantity:4batteriesrequired
•Voltage:
-120Vversion(FG678-15):24VDC
-240Vversion(FG678-20):48VDC
•InRushCurrent:
-120V:<40A
-240V:>20A
•RechargeTime:2–4hoursto90%
•Storage:Storeat-15to+30°C(+5to+86°F),chargetheUPSbatteryevery
6months/Storeat+30to+45°C(+86to+113°F),chargetheUPSbattery
every3months.
LED INDICATORS
•Utilitymode
•Backupmode
•Batteryconditions
DISPLAY LCD
•Loadlevel(%)
•Batterylevel(%)
•Bypass
•AVR-Boost/AVRBuck
•BatteryLow/Replace/Fault
•UPSFault
•SiteWiringFault
•Overload
OVERLOAD PROTECTION
•ACMode:>110%Buzzercontinuouslyalarms,andshutsdownin10minutes.
•InverterMode:>120%Buzzercontinuouslyalarms,andshutsdownin
10seconds.
SHORT CIRCUIT PROTECTION
•ACMode:Breakerandelectroniccircuit
•Maxshortcircuitoutputcurrent:
-120V:50A,8cycles(InverterModeshortcircuitcurrentlimitation)
-240V:25A,8cycles(InverterModeshortcircuitcurrentlimitation)
SELF-DIAGNOSTICS
Upon Power-on
ALARMS
•LineFailure
•BatteryLow
•OverloadandFault
ENVIRONMENTAL
•Temperature:32°to104°F(0to40°C)
•OperationHumidity:95%RHMaximum,non-condensing
CONTROL COMMUNCATION
RS-232
CERTIFICATIONS
•EN50091-1-1:1996(Safety)
•FCCPart15,SubpartB-ClassA
•UL:YEDU.E166979
INCLUDED ACCESSORIES
•ACInputPowerCord
•Towerandrack-mountingaccessories