Instruction manual
15
I N S T A L L E R S e c t i o n ( e n )
7108686.02 (1-11/12)
(a) (b)
ZONE 1 HEATING PARAMETERS (main zone)
Factory
setting
Minimum Maximum
P01 700 *Operating mode (0=Frost Protection, 1=Timed, 3=T.comfort) - 3 0 3
P02 712 *Reduced ambient temperature °C 16 4 35
P03 720 *“Kt” curve slope - 1,5 0,1 4
P04 721 *“Kt” curve drift - 0 - 4,5 4,5
P05 726 *“Kt” curve adaptation (0=off) - 1 0 1
P06 740 Flow temperature setpoint (minimum value) °C 25 8 80
P07 741 Flow temperature setpoint (maximum value) °C 80 25 80
P08 742 *Enable modulating temperature if set = “---” °C 80 25 80
P09 750 *Room inuence (“---” = disabled) % 50 1 100
P10 834 *Opening/Closing speed of mix valve S 180 30 873
ZONE2 HEATING PARAMETERS (with accessory Expansion Unit)
P11 1000 *Operating mode (0= Frost Protection, 1=Timed, 3=T.comfort) °C 3 0 3
P12 1010 *Comfort room temperature °C 20 4 35
P13 1012 *Reduced room temperature °C 16 4 35
P14 1020 *“Kt” curve slope - 1,5 0,1 4
P15 1021 *“Kt” curve drift - 0 - 4,5 4,5
P16 1026 *“Kt” curve adaptation (0=off) - 1 0 1
P17 1040 Flow temperature setpoint °C 25 8 80
P18 1041 Flow temperature setpoint (maximum value) °C 80 25 80
P19 1042 *Enable modulating temperature if set = “---” (ow temp. setpoint if P63=0) °C 80 25 80
P20 1050 *Room inuence (“---” = disabled) % 50 1 100
P21 1134 *Opening/Closing speed of mix valve
s
180 30 873
DHW PARAMETERS
P22 1620
Operating mode in DHW (with Remote Control)
- 0 0 20=always enabled, 1=according to hourly heating programme,
2= according to hourly DHW programme.
P23 1640
Anti-legionella function Disabled
- 0 0 1
0=disabled, 1=periodic (depending on P24)
P24 1641
Periodic anti-legionella function enable (only if P23 =1)
- 7 1 7
1=daily, 2..6=intervals of 2..6 days, 7=once a week
P25 1663 Circulation temperature setpoint (additional DHW pump) °C 45 8 80
P26 5470 Preheating time for DHW circuit (1=10’ -- 144=1440’) min 0 0 144
BOILER PARAMETERS
P27 2243 Minimum boiler off time min 3 0 20
P28 2217 Frost Protection setpoint °C 5 -20 20
P29 2250 Pump post-circulation time min 3 0 240
P30 2441 Max. fan speed (heating) rpm xxx 0 8000
P31 2455 Minimum boiler off differential °C 10 0 20
SOLAR PLANT PARAMETERS (with accessory Expansion Unit)
P34 3810 Temperature - on differential °C 8 0 40
P35 3811 Temperature - off differential °C 4 0 40
P36 3830 Collector start function (“---” = disabled) min --- 5 60
P37 3850 Solar panel manifold overheating protection (“---“ = disabled) °C --- 30 350
P38 5050 DHW charging temperature max °C 65 8 95
P39 5051 Maximum temperature of storage tank
°C
90 8 95
CONFIGURATION
P40 5700 Not used (Do NOT change this parameter)
-
--- --- ---
P41 5710 Zone 1 heating circuit (1=enabled) - 1 0 1
P42 5715 Zone 2 heating circuit (1=enabled)
-
0 0 1
P43 5730 DHW sensor (1=Tank sensor, 2=Thermostat, 3=instantaneous sensor) 1 1 3
P44 5890 Not used (Do NOT change this parameter) - 33 0 43
P45 5931 *BX2 sensor input (rst auxiliary sensor – section 11)
-
0 0 19
P46 5932 *BX3 sensor input (second auxiliary sensor – section 11) - 0 0 19
P47 5977 *Input H5 (multifunction input – 18=Room thermostat)
-
18 0 32
P48 6020 *Conguration of accessory Expansion Unit - 0 0 7
P49 6024 Function input EX21 module 1 (conguration of HC Safety Thermostat) - 0 0 1
P50 6046 Function input H2 module 1 (multifunction input)
-
0 0 58
P51 6097 Sensor type collector (1= NTC, 2= Pt 1000) - 2 1 2
P52 6110 Building time constant h 15 0 50
P53 6220 Software version - --- 0 99
P54 6600 LPB device address - 1 16
P55 6601 LPB segment address - 0 14
P56 6640 Clock time source - 0 3