11.2.8 AGU 2.550
Use the AGU 2.550 , already installed in the boiler, to send information from the boiler
as described below to a BMS panel.
ELECTRICAL CONNECTION
X1 (L-N)
Power supply (230V 50Hz AC) connected to the boiler terminal
block M1 (C+M)
X1 (QX21) Not used
X1 (QX22-N) Boiler OPERATION (light on = run)
X1 (QX23-N) Boiler ALARM (light on = lockout)
X2 (H2-M) INPUT Electrical Signal 0÷10 V
12. SPECIAL FUNCTIONS
12.1 SYSTEM AIR EXTRACTION FUNCTION
This function is used to facilitate the elimination of the air inside the heating circuit when the boiler is rst installed or after mainte-
nance when the water is drained from the primary circuit and re-lled.
To enable the system air extraction function press buttons
together for 6 seconds. When the function is active, On appears on the display for a few seconds, followed by programme
row 312.
The electronic board will activate a pump on/off cycle lasting 10 minutes. The function will automatically stop at the end of the
cycle. To manually exit this function, press the above buttons together for 6 seconds once again.
12.2 COMMISSIONING FUNCTION
To commissioning the gas valve, proceed as follows:
Press buttons and together for at least 6 seconds. When the function is enabled, the displays shows Onfor a few
seconds followed by programme row “304” alternated with the % of boiler power.
Press to gradually adjust power (sensitivity 1%) 100% for high re and 0% for low re.
To exit press both buttons together for at least 6 seconds, as described in point one.
Press to display the instantaneous ow temperature for 15 seconds.
12.3 CHIMNEY SWEEP MODE
When this function is enabled, the boiler generates maximum heating power. To enable the function, proceed as follows:
press together for 6 seconds. The display shows “303” alternated with the power output of the boiler.
Press and to adjust boiler power 1=minimum, 2=maximum DHW, 3=maximum heating.
To exit press both buttons together for at least 6 seconds, as described in point one.
13. FAULTS THAT CANNOT BE RESET BY THE USER
In case of FAULTS that cannot be reset by pressing (such as E151 or exceeding 5 manual
RESET attempts by the user) RESET the board by pressing the black button ( R) located under
the rubber cap (symbol ) of the front control panel (gure to side).
14. PARAMETER SETTINGS
To programme the parameters of the boiler electronic board, proceed as follows:
Press together and hold them down for 6 seconds until programme row P02” appe-
ars on the display alternated with the set value (°C);
Press and hold down for 6 seconds until On” appears on the display. Release the but-
ton and “P01” appears on the display;
Press to scroll the list of parameters;
Press , the value of the selected parameter begins ashing, press to change the value;
Press to conrm the value or press to exit without saving.
Further information concerning the parameters listed in the following table are supplied together with the required acces-
sories.
0÷10 V
Input Signal
CG_2241
~
230 V
(Boiler M1)
3
ALARM (LOCKOUT)
SIGNAL LAMP 230V
STATUS (RUN)
SIGNAL LAMP 230V