Specifications
XP600/1100 INSTALLATION AND OPERATION MANUAL
APPENDIX A
XP-600 / 12VDC
13.8 VDC
10.4 / 10.6 VDC
16.5 VDC
58.8 A 66.6 A
XP-600 / 24VDC
27.6 VDC
19 / 21 VDC
33 VDC
29.4 A 33.6 A
XP-600 / 48VDC
55.2 VDC
41.5 / 42.5 VDC
62 VDC
14.7 A 16.6 A
XP-600 / 66VDC
75.9 VDC
57.5 / 58.5 VDC
91 VDC
10.7 A 12.1 A
XP-600 / 108VDC
124.0 VDC
94 / 95 VDC
149 VDC
6.5 A 7.4 A
MODEL
NORMAL
VDC
MINIMUM VDC
CUT-OFF / ALARM
MAXIMUM
VDC
RATED
CURRENT
PEAK
CURRENT
XP-600 / 12VDC
MODEL
Input Power Requirements:
Recommended Input Wire Sizes (For Variable Distances from the Battery):
4 AWG
LESS THAN 5’
0 AWG
LESS THAN 10’
0 AWG
LESS THAN 15’
00 AWG
LESS THAN 20’
XP-600 / 24VDC 10 AWG 6 AWG 4 AWG 4 AWG
XP-600 / 48VDC 16 AWG 12 AWG 10 AWG 10 AWG
XP-600 / 66VDC 18 AWG 16 AWG 14 AWG 12 AWG
XP-600 / 108VDC 18 AWG 18 AWG 18 AWG 16 AWG
Note: The table specifies standard wire sizes (not smaller than 18 AWG) that will provide less than a
2% voltage drop at Low-line Input voltage and Rated Output Power.
XP-1100 / 12VDC
13.8 VDC
10.4 / 10.6 VDC 16.5 VDC
107.8 A 122.1 A
XP-1100 / 24VDC
27.6 VDC
19 / 21 VDC 33 VDC
53.9 A 61.6 A
XP-1100 / 48VDC
55.2 VDC
41.5 / 42.5 VDC 62 VDC
27 A 30.5 A
XP-1100 / 66VDC
75.9 VDC
57.5 / 58.5 VDC 91 VDC
19.6 A 22.1 A
XP-1100 / 108VDC
124.0 VDC
94 / 95 VDC 149 VDC
12 A 13.6 A
XP-1100 / 12VDC 0 AWG 00 AWG 0000 AWG 0000 AWG
XP-1100 / 24VDC 6 AWG 4 AWG 2 AWG 0 AWG
XP-1100 / 48VDC 12 AWG 10 AWG 8 AWG 6 AWG
XP-1100 / 66VDC 16 AWG 12 AWG 10 AWG 10 AWG
XP-1100 / 108VDC 18 AWG 16 AWG 14 AWG 14 AWG
Page 15