Specifications
ALARMS
Internal protection circuitry will disable the supply output, and
cause the form-C alarm relay contacts to go to the NO/NC
alarm state for the following conditions:
Internal temperature too high (will automatically reset
when cool)
Input ac voltage out of range (resets when in range)
Output voltage too high (cycle power to reset)
Battery voltage too high (resets when voltage in range)
Internal System Fail (resets if internal fault clears)
SPECIFICATIONS
Input Voltage: 100 – 264Vac 50/60Hz
Input Power Factor: 0.99 (120Vac input)
V-output Line Regulation: +/- 0.1%
V-output Load Regulation: +/- 1%
Operating Temperature: -20°C to 60°C
2
Output Grounding: Positive, Negative or floating
Efficiency: 88% typical (120Vac)
Remote Shutdown: 2.5 to 16V signal
Form-C Alarm relay: 0.5A 125Vac/dc max
EMC: Meets FCC part 15 class B limits
1
With LVD Option installed, factory default levels shown.
2
Reduce output current 10% for ambient above 50C
LIMITED WARRANTY
ICT Ltd. warrants to the original consumer purchaser that this
product shall be in good working order, free from defects in
materials and workmanship, for a period of three (3) years from
the date of purchase. Should failure occur during the above
stated time period, then ICT will, at its option, repair or replace
this product at no additional charge except as set forth below.
All parts, whether for repair or replacement, will be furnished
on an exchange basis. All exchange pieces become the property
of ICT. This limited warranty shall not apply if the ICT product
has been damaged by unreasonable use, accident, negligence,
disaster, service, or modification by anyone other than the ICT
factory.
Limited warranty service is obtained by delivering the product
during the above stated three (3) years warranty period to an
authorized ICT dealer or ICT factory and providing proof of
purchase date. If this product is delivered by mail, you will
insure the product or assume risk of loss or damage in transit,
and prepay shipping charges to the factory.
Every reasonable effort has been made to ensure that ICT
product manuals and promotional materials accurately describe
ICT product specifications and capabilities at the time of
publication. However, because of ongoing improvements and
updating of ICT products, ICT cannot guarantee the accuracy of
printed materials after the date of publication and disclaims
liability for changes, errors or omissions.
If this ICT product is not in good working order, as outlined in
the above warranty, your sole remedy shall be repair or
replacement as provided above. In no event will ICT be liable for
any damages resulting from the use of or the inability to use the
ICT product, even if an ICT employee or an authorized ICT
dealer has been advised of the possibility of such damages, or
for any claim by any other party.
ICT reserves the right to make changes without further notice to
any products or documentation for improvement of reliability,
function, or design.
ICT Ltd. does not recommend use of its products in life support
applications wherein a failure or malfunction of the product
may directly or indirectly threaten life or cause injury. The user
of ICT products, which are to be used in life support applications
as described above, assumes all risks of such use and
indemnifies ICT against all damages.
Model:
ICT690-12
ICT690-24
ICT690-48
Output Voltage
(Nominal, +/-
0.5%)
13.8V
27.6V
55.2V
Output Current
Limit (min-max)
50.0 – 52.5A
25.0 –
26.25A
12.5 – 13.1A
Output V Noise
(max)
20 mVrms
30 mVrms
60mVrms
Input Current
max at 100Vin
9A
9A
9A
Max Voltage for
full current out
13.8V
27.6V
55.2V
LVD Disconnect
point (+/- 2%)
1
10.5
21.0
42.0
LVD Reconnect
point (+/-2%)
1
12.0
24.0
48.0
Output Power
(max rated)
690W
690W
690W
ICT690-12S/ICT690-12SB
ICT690-24S/ICT690-24SB
ICT690-48S/ICT690-48SB
PRO SERIES POWER SUPPLY