Instruction manual

29
text message notification to a cell phone. See the Text Message
Alarm Notifications section for more information.
"To" E-mail Address #2:
If you would like a second e-mail address
to receive the e-mail notifications, enter it here. If this field is used, a
valid e-mail address must also be entered in the β€œTo” E-mail Address
#1 field.
SMTP User Name: If your SMTP server requires a user name and
password, enter the user name here. Leave this field blank if your
SMTP server does not require authentication.
SMTP Password:
If your SMTP server requires a user name and
password, enter the password here. Leave this field blank if your
SMTP server does not require authentication.
Enable SNMP: Contact the factory if you would like information on
using an SNMP system to monitor the power supply output.
5.5.
Alarm Setup
This page allows you to choose which alarms you wish to activate.
To save any changes to the alarm settings, click on Save Settings
at
the bottom of this page. (Note: For Digital Series units without the
Ethernet option the form C relay output will always be activated for an
alarm condition.)
The e-mail settings on the
Network Setup
page must be configured
correctly before any e-mail notifications can be sent.
5.5.1.
DC OUTPUT FAILURE ALARM
Activate Alarm Form C Contact: If this box is checked, the alarm
form β€œC” contacts on the power supply will indicate a fault condition
when the Output Voltage or current rises above approximately 110%
of the max-rated output.
Send E-mail: If this box is checked, an e-mail alarm notification will
be sent when a DC output failure occurs.
The alarm latches the output off, and clears when the DC output is
manually re-enabled.
5.5.2. AC UNDER VOLTAGE/SYSTEM FAILURE ALARM