Instruction manual

26
•
Output Voltage:
This field sets the DC output voltage of the
power supply within the allowable range.
•
Current Limit:
This field sets the DC output current limit of the
power supply within the allowable range.
Device Name: Enter a unique name for the power supply if desired.
Auto-Restart Delay:
Set delay time (5 to 240s) that output will
remain off when output is remotely disabled using the Auto-Restart
button. The unit will then automatically restart after the Restart Delay
period.
Parallel Operation:
Configure the unit as the master, or a slave unit
within parallel connected sets. Also set a unique ID number for each
parallel unit (required) and enable parallel slave unit alarm e-mails if
desired. See section 4.4 Advanced Parallel Operation with TCP/IP
Ethernet Option for more information.
5.3.
Battery Backup
This page is only available if the power supply has the “Battery
Backup” LVD option “B” installed.
This page allows you to configure the backup options of the power
supply. To save any settings changes, click on Save Settings
at the
bottom of this page.
5.3.1.
LVD (Low Voltage Disconnect) SETTINGS:
Disconnect Voltage: If the battery voltage drops below the value in
this field, the battery relay will open and disconnect the battery.
Reconnect Voltage: If the battery voltage rises above the value in
this field while the battery is disconnected, the battery LVD relay will
close and reconnect the battery.
Form C Contact:
The alarm will be activated due to any failure of the
AC input, this function cannot be disabled.
5.3.2.
BATTERY FAULT ALARM
Activate Alarm Form C Contact: If this box is checked, the alarm
form “C” contacts on the power supply will indicate a fault condition
when the LVD module detects that the battery voltage it outside the