Instruction manual

17
Reconn Voltage:
Modifies the battery reconnect voltage. If the
battery voltage rises above the reconnect voltage while the battery is
disconnected, the battery relay will close and reconnect the battery.
There will be a 3 seconds delay until the voltage connects. The
Range of the Disconnect Voltage is 10.6- 13.8V. (12V model)
3.4.
Control Panel Menu Password Reset
This procedure clears the Control Panel menu password and allows you to
set a new password if needed. To clear the password, do the following:
1. Turn the Power Switch to the OFF position.
2.
Press and hold down the Back and Enter keys. Turn the Power
Switch to the ON position while holding the keys down. Continue
holding the keys down for 15 seconds until the System Status
screen is displayed on the Control Panel display.
3. Release the Back and Enter keys. You will no longer be
prompted for a password on any of the Control Panel screens.
4. In order to set a new password see SECURITY SETTINGS
SCREEN on page 14.
3.5.
Administrator Password / IP Address Reset
This procedure resets the Administrator password, IP address, and port
settings to the original factory default values. The Standard User password is
not affected. To reset, do the following:
1. In the Control Panel menu on the front of the power supply, go to the
Comm Settings
screen and press the Enter key.
2. Scroll down to Reset Comm Settings
and press the Enter key.
3. Turn the Encoder Wheel to select Yes
, and then press the Enter key.
4. After reset is complete, go to the Network Status
screen in the Control
Panel menu to view the new IP address of the power supply.