PARALLEL SETTINGS
MODE: STANDALONE
DEVICE ID: 0
UNITS IN PARALLEL: 0
See the
Smart
Parallel Operation
section for more information on
configuring the parallel settings.
Parallel Mode:
Modifies the parallel mode setting. It has 3 options:
Standalone:
Single Unit.
Slave and Master:
Parallel Units.
Device ID: Modifies the parallel device ID setting. Ranges from 0 – 5.
Units In Parallel:
If parallel operation is active, the total number of
parallel units is displayed on this line. If parallel operation is not
active, the display will show blank. Up to 6 Units can be connected in
parallel corresponding to the value 0 – 5.
3.3.6. LVD SETTINGS SCREEN
LVD SETTINGS
DISCON VOLTAGE: 10.5V
RECONN VOLTAGE: 12.5V
BATT VOLTAGE: 0.0V
The LVD Settings screen is only available if the Battery Backup
option (“B”) is installed.
Disconn Voltage: Modifies the battery disconnect voltage. If the
battery voltage drops below the disconnect voltage, the battery relay
will open and disconnect the battery. There will be a 3 seconds delay
until the voltage disconnects. The Range of the Disconnect Voltage is
10 – 12.4V. (12V model)