Specifications

30 31
Electrical Testers
30
Wiring Testers Test wiring in seconds
INSP-3 Wiring Inspector
Just plug in this rugged tester and in seconds you can verify whether a
building’s wiring complies with electrical code, especially voltage drop under
load. Identify issues crucial to the safety and performance of an electrical
system such as splices, connections and conductor quality.
Save time and money by testing more efficiently: a single large display shows all relevant
test data (voltage, voltage drop, hot and neutral voltage drop, voltage with load, ground
impedance). No scrolling or switching screens needed
Find faulty wiring that needs repair without removing outlet cover plates or panel covers, including:
- Faulty splices and connections
- Incorrect wiring
- Undersized wiring
- Faulty GFCIs
- Faulty or incorrectly wired AFCIs
- Incorrect line voltage
- Poor ground quality
Verify performance of electrical systems with user selectable 10,15 and 20 amp loads
Flashing screen clearly indicates incorrect wiring or voltage drop test failure
Test without tripping circuit breakers or blowing fuses
Check grounding for safety and ability to support sensitive electronic equipment
Measure fault currents
INCLUDED ACCESSORIES: Power cord, 9 V alkaline battery (Installed), users manual, carrying case
FEATURE INSP-3 BEST ACCURACY
Load:
Constant 10, 15 or 20 AMP
simulation regardless of line voltage
-
Operating Voltage:
95 VAC
^
140 VAC +/- 2 % + 2 digits
GFI Trip:
6.0 mA nominal to trip GFI,
30 mA to trip RCD
-
AFCI Trip:
Up to 8, 120 AMP pulses
within 1/2 second period
-
NEW
Electrical Testers
User-friendly troubleshooters for voltage and continuity Voltage and Continuity Testers
FEATURE VPC-30 VPC-31
AC Voltage
24 V, 48 V, 120 V, 208 V, 240 V, 277 V, 347 V,
480 V, 600 V, 1000 V
24 V, 48 V, 120 V, 208 V, 240 V, 277 V, 347 V,
480 V, 600 V, 1000 V
DC Voltage
6 V, 12 V, 24 V, 36 V, 48 V, 60 V, 72 V,
110 V, 220 V, 380 V
6 V, 12 V, 24 V, 36 V, 48 V, 60 V, 72 V,
110 V, 220 V, 380 V
Continuity
Built in Shaker
-
VolTect
Non-Contact
Voltage Detection
LCD Display with Backlight
-
Super-bright bi-color LEDs indicates safe and dangerous voltages (above 55VDC or 30VAC)
LEDs indicate 10 levels of AC and DC Voltages:
- Volts (AC) 24, 48, 120, 208, 240, 277, 347, 480, 600, 1000
- Volts (DC) 6, 12, 24, 36, 48, 60, 72, 110, 220, 380
Auto hold feature keeps LEDs illuminated to retain a reading for 10 seconds after leads are
disconnected
Solenoid tester-like shaker indicates AC voltage presence
Auto backlit LCD digital display for precise voltage measurements (VPC-31 only)
VolTect
non-contact voltage detection
Continuity buzzer and visual continuity indication (LED)
Tests GFCI receptacles and breakers
Automatically turns on and off for easy and quick measurements
Automatically selects ac voltage, dc voltage or continuity
Water- and dust-proof, IP65 design
Standard detachable test lead for easy replacement with optional longer or specialized probe
VPC-30 and VPC-31 Voltage Tester
For live voltage and continuity checks, these rugged and easy-to-use testers
offer a built-in shaker with the same functionality and feel as older analog
solenoid testers. Yet, they provide full input protection to CAT IV 600V /
CAT III 1000V.
VPC-30
VOLTAGE & CONTINUITY TESTER
VPC-31
VOLTAGE & CONTINUITY TESTER
INCLUDED ACCESSORIES: Users manual, batteries (installed), test lead
DUAL RATED
NEW
ORDERING INFORMATION
ORDERING INFORMATION
For detailed specifications
go to www.Amprobe.com
INSP-3
WIRING INSPECTOR
ORDERING INFORMATION
For detailed specifications
go to www.Amprobe.com