Specifications

22 23
DMMs
Industrial Multimeters - Work safely with the right meter
AM-270 and AM-250 Multimeters
If your electrical or HVAC applications take you outdoors or if you work on
wiring directly connected to utility transformers or main panels, your meter’s
CAT safety rating is important. The AM-270 is rated CAT IV 600V / CAT III
1000 V. For indoors only, choose the CAT III 600V / CAT II 1000V rated
AM-250. Both models measure a complete range of electrical parameters plus
temperature, capacitance and a micro amps function for HVAC.
N10140
INCLUDED ACCESSORIES: Test leads (pair),
banana plug K-type thermocouple, batteries
(installed), users manual
Auto and manual ranging
Data hold
Audible continuity
Large, easy-to-read LCD display with backlight
Diode test and relative zero mode (AM-250 only)
Peak hold with 30ms response time (AM-250 only)
Beep-Jack audible warning against improper connection (AM-250 only)
True-rms provides accuracy and dependability (AM-270 only)
FEATURE AM-250 AM-270
AC Voltage
400.0 mV, 4.000 V, 40.00 V,
400.0 V, 1000 V
50.00 mV, 500.0 mV, 5.000 V,
50.00 V, 500.0 V, 1000 V
DC Voltage
400.0 mV, 4.000 V, 40.00 V,
400.0 V, 1000 V
50.00 mV, 500.0 mV
5.000 V, 50.00 V, 500.0 V, 1000V
Resistance
400.0
Ω,
4.000 k
Ω,
40.00 k
Ω,
400.0 k
Ω
4.000 M
Ω,
40.00 M
Ω,
50.00
Ω,
500.0
Ω,
5.000 k
Ω,
50.00 k
Ω,
500.0 k
Ω
, 5.000 M
Ω,
50.00 M
Ω
AC / DC Current
40.00 µA, 400.0 µA, 400.0 mA,
4000 mA, 4.000 A, 10.00 A
50.00 µA, 500.0 µA, 500.0 mA,
5000 mA, 5.000 A, 10.00 A
Frequency
5.000 Hz, 50.00 Hz, 500.0 Hz,
5.000 kHz, 50.00 kHz,
500.0 kHz, 1.000 MHz
5Hz
^
125 kHz for all setups except:
5Hz
^
1kHz for 500V and 1000V ranges
5 Hz
^
20 kHz for 50 V range
Capacitance
500.0 nF, 5.000 µF, 50.00 µF,
500.0 µF , 3000 µF
50.00 nF, 500.0 nF 5.000 µF,
50.00 µF, 500.0 µF, 9999 µF
Temperature
-4 ˚F
^
572 ˚F (-20 ˚C
^
300 ˚C) -58 ˚F
^
1832 ˚F (-50 ˚C
^
1000 ˚C)
Data Recording
Records peak, max, min, max-min
Relative Zero Mode
DMMs
AM-140-A and AM-160-A True-rms Precision
Digital Multimeters with PC Connection
These true-rms commercial-grade digital multimeters offer more features
and better accuracy at a great price. Frequency, capacitance, duty cycle,
temperature, analog bar graph and PC interface are just a handful of features
available on these meters.
Precision accuracy to 0.02% (AM-160-A only)
High speed analog bar graph
Dual temperature (AM-160-A only)
Optical isolated PC interface for safe data downloads
Crest (peak hold), min/max, max-min recording
Audible continuity
Auto and manual ranging
Intelligent auto power off
Data hold
Relative zero mode
Audible and visual warning against improper plug-in
Large, easy-to-read LCD display with back light
True-rms provides accuracy and dependability
High performance at a great price
– Precision Digital Multimeters
AM-140-A
PRECISION TRUE-RMS
DIGITAL MULTIMETERS WITH
PC CONNECTION
AM-160-A
PRECISION TRUE-RMS
DIGITAL MULTIMETERS WITH
PC CONNECTION
N10140
INCLUDED ACCESSORIES: battery (installed), users manual, test leads,
type-K thermocouple (AM-160-A only)
FEATURE AM-140-A AM-160-A BEST
ACCURACY
AC Voltage
500.00 mV , 5.0000 V, 50.000 V, 500.00 V, 1000.0 V
+/- (0.08 % rdg + 60 LSD)
@ 45 Hz
^
300 Hz
DC Voltage
500.00 mV, 5.0000 V, 50.000 V, 500.00 V, 1000.0 V
+/- (0.03 % rdg + 2 LSD)
@ 0 V
^
50 V
Resistance
500.00
Ω
, 5.0000 k
Ω
, 50.000 k
Ω
, 500.00 k
Ω
,
5.0000 M
Ω
, 50.000 M
Ω
+/- (0.10 % rdg + 6 LSD)
AC / DC Current
500.00 µA , 5000.0 µA; 50.000 mA, 500.00 mA;
5.0000 A, 10.000 A
+/- (1.0 % rdg + 40 LSD)
@ 50 Hz / 60 Hz
Frequency
5.0000 Hz
^
200.000 kHz +/- (0.002 % rdg + 4 LSD)
Capacitance
50.00 nF, 500.0 nF, 5.000 µF, 50.00 µF, 500.0 µF, 9999 µF
+/- (2.0 % rdg + 3 LSD)
@ 50 nF
^
50 µF ranges
Temperature
Dual thermocouple
-58 ˚F
^
1832 ˚F
(-50 ˚C
^
1000 ˚C)
+/- (0.3% rdg + 2 ˚F),
+/- (0.3% rdg + 1 ˚C)
Duty Cycle
0.1 %
^
99.99 % +/-(3 LSD / kHz + 3 LSD)
RECOMMENDED ACCESSORIES
DL248D Deluxe Test Leads Kit
(See Page 76)
CT235A Clamp Attachment
CT237B Clamp Attachment
CT238A Clamp Attachment
(See Page 77)
USB KIT3 PC Software and
Connection Kit
(See Page 79)
DUAL RATED
AM-270 only
DUAL RATED
Do you need CAT IV?
The closer you work to a power source, the
greater the protection your test tools must
provide. You need CAT IV safety-rated tools
if you’re:
• Makingmeasurementsoutdoors
• Workingonwiringthatconnectsbuildingstoutility
transformers
• Directlyconnectingtothemainpanel,indoors
For additional information about CAT environments,
see our Safety Reference Guide, page 36.
DUAL RATED
AM-250 only
RECOMMENDED ACCESSORIES
DL248D Deluxe Test Leads Kit
(See Page 76)
CT235A Clamp Attachment
CT237B Clamp Attachment
CT238A Clamp Attachment
(See Page 77)
ORDERING INFORMATION
For detailed specifications
go to www.Amprobe.com
ORDERING INFORMATION
For detailed specifications
go to www.Amprobe.com
AM-270
TRUE-RMS INDUSTRIAL
MULTIMETER
AM-250
PROFESSIONAL ELECTRICAL
MULTIMETER
NEW