Service manual
MDS E-SCAN MPR E-SCAN /INSTALLATION
9
MDS E-Scan NEMA 4X Console
1. MDS E-Scan Installation
1.1 Site Selection
The MDS E-Scan cabinet can be mounted in any area
where ambient conditions allow personnel to remain
for extended periods and is suitable for the atmosphere
and service conditions normal to a recovery boiler
installation. A vortex cooler or a cooling fan is
supplied with the cabinet to prevent excess heat build-
up. The cabinet should be kept closed to maintain
environmental resistance.
1.2 Power Requirements
The electrical power supply to the refractometer
system must be from a dependable non-interrupted
source. It is suggested that the power supply be the
same as that used for the auxiliary burner safeguard
system and the black liquor firing safety system. We
recommend that cables be run in conduit.
Note: The MDS E-Scan system is designed for a 120VAC power supply. If other voltages are
used, a transformer must be supplied.
Once the cabinet is fastened securely in place, the interconnecting wiring may be run between
TB13 and the control room. Use the interconnection diagram supplied in this manual for running
the interconnecting wiring. Close observance of the required shielding will ensure proper
operation of the Monitor. Signal wires should be kept separate from “POWER IN” and
“RELAY CIRCUITS” to the control room. After completing the interconnection wiring,
carefully recheck all connections to satisfy yourself that all are correctly terminated.
Important: Prior to shipment of an MDS E-Scan system, the sensing heads are
matched to the consoles and factory calibrated. DO NOT ATTEMPT TO CALIBRATE!