ZoneSense PLUS Fire Alarm Control Panel EN54 2 & 4 1997 Installation, Commissioning & Operation MAN 2326-12
FIRE BRIGADE RESPONSE GUIDE INCOMING ALARM CONDITION 1. INDICATION ZONE 7 FIRE LED STEADY FIRE FIRE 2. ZONE 7 ZONE 8 SOUNDER SILENCE OR SOUND EVACUATION ALARMS SILENCE RESOUND Z7 : ALARM SU 14:45 EVACUATE Access to these controls is restricted by a Password / Panel Keyswitch For multiple Zones in Alarm repeat the above steps after pressing. to step to the next Zone in Alarm. Z7 : DISABLE SU 14 46 3. SOUNDER SILENCE / SOUNDER RESOUND PRESS SILENCE / RESOUND TO SILENCE ALARMS.
TABLE OF CONTENTS 1 2 About This Manual ............................................................................................................... 1 1.1 Purpose ..................................................................................................................... 1 1.2 Scope ........................................................................................................................ 1 1.3 References........................................................................
6.10.4 7 Reset Terminal / Buzzer Output. TB12/3 ..................................................... 17 Adding Control and Monitoring Facilities ......................................................................... 18 7.1 Internal Communications Connector (RS485) ........................................................... 18 7.2 Installation and Cabling of Add On Cards & Boards .................................................. 18 7.3 Terminating the Communications Bus ..........................
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION 1 About This Manual 1.1 Purpose This manual is an instructional tool for the installation, commissioning, programming / reprogramming and operation of the ZoneSense PLUS Fire Alarm Control Panel (FACP). 1.2 Scope The information within this manual is only available to and for the use of personnel engaged in the installation and operation of the ZoneSense PLUS FACP. ZoneSense PLUS has been designed to comply with major world standards.
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION 2 Introduction The ZoneSense PLUS 4, 8 zone FACP complies with the highest level of approval for any applicable code and can be connected to an appropriate Fire Service monitoring facility. As a Minimum, the conventional panel meets the following Standards; British Standard European Standard BS 5839 EN54 Parts 2 & 4 The basic ZoneSense PLUS is available in a ABS (BX1) and Metal (BX10) cabinets and consists of a; 1.
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION 3 Mechanical ZoneSense PLUS can be surface or semi-flush mounted. The ABS version is supplied with a detachable door, a mountable back box. Depending on the configuration it may be necessary to remove the batteries to expose the lower mounting keyhole. All of which are easily removed should it be necessary. Inside the door is a matrix style label for the recording of the panel configuration. 3.
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION 163.20 mm 147.00 mm 147.
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION 230.90 mm 288.
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION 3.1.2 PCB Removal / Replacement If the PCB’s have to be removed the following precautions should be observed; 1. Removing the door will provide better access to the boards and ensure the hinges are not accidentally stressed. 2. Personal anti- static procedures must be followed. 3. When disconnecting the telecom style (RJ45) connecting cable from the PCB, make sure that the cable remains connected to at least one board to prevent it being misplaced.
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION 3.1.3 Removing the Knockouts Carefully decide how the wiring will be brought into the panel then remove the required knock-outs for the bushes and cables. The knock-outs should be removed with a sharp tap in the rim of the knock-out using a flat broadbladed screwdriver. Use of excessive force could damage the enclosure around the knock-out. Always ensure if a knock-out is removed, the hole is filled with a good quality cable gland.
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION 4 Electrical 4.1 Primary Power Supply The Power Supply is; A switch-mode design and operates from a mains supply of: 90VAC - 264VAC @ 47Hz 63Hz; Capable of supplying the system while all zones are in alarm; and 4.1.1 Mains wiring The requirement for the Mains supply to the FACP is fixed wiring, using three core cable (no less than 0.75mm² and no more than 2.
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION Chassis Earth Terminal Note: * Extra M4 Nut and M4 SPW are provided finger tight on the Earth bolt. M4 Nut * M4 Shake Proof Washer * Earth Cable Earth Cable Figure 10: Chassis Earth Terminal Connection 4.
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION 4.3.1 Connecting the Stand-By Batteries Two new, good quality and fully charged 12V Sealed Lead Acid batteries are required as the emergency stand-by power supply for the Panel. They are to be mounted in the bottom of the cabinet. In the ABS version a protective tray is supplied in the packaging. The batteries should be connected in series using the series link wire provided and located within the panel enclosure.
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION Main Control Card BRD25MCB –A (4 Zone) B (8 Zone) The Main Control Card and its front display panel combined with the Power Supply / Battery Charger / batteries form the basis for the ZoneSense PLUS FACP.
INPUTS RS485 COM SP C/C ALT TB3 - TB2 + S P A R E Class Change Input EOL Capacitor Rear of Main Board CN6 PSU Control from CN2 of the P/S CN8:27V In from CN4 of the P/S CN10: 27V Out to Internal Cards & Boards TB14 + Z5 - + Z6 - + Z7 - + Z8 - DETECTOR ZONES Open Collector O/Ps Current Limited to 25mA.
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION Figure 13: Simple Wiring Diagram of the Basic FACP 6 Wiring to the Main Card BRD25MCB 6.1 Earth Monitoring The earth monitoring disable/enable feature is accessible via the SYSTEM menu at access level 3. Disabling the earth monitoring does not illuminate the Earth Fault LED on the control panel.
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION 6.3 TB3 Inputs Common Terminal TB3 Used with the inputs 0v potential. Spare Input TB3 /1 Not used (Monitored input defaults to general alarm as explained below). Class Change Input TB3 / 2 Input is provided to allow a remote connection to operate the sounder alarm outputs. The input is active when it is pulled down to 0v potential.
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION 6.5 Zone Circuit Wiring TB13 - 14 Zone circuit connections are made directly to TB13 & TB14 on the Main Card and if screened cabling is used the screen is terminated at the panel's chassis earth terminal. Reminder 1: A maximum of 32 ZoneSense PLUS compatible Optical / Heat Detectors or Manual Call Points can be fitted to each circuit and mixed in any order.
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION 6.7 Conventional Sounder Circuit Wiring The four alarm outputs can be used for conventional sounder circuits. Note: All Sounders must be polarised. An end of line resistor (10kΩ) must be connected at the end of each circuit to allow the wiring to be monitored. The wiring for each circuit is connected to the relevant 5mm connector block on the Main Control PCB and the screens terminated to the chassis earth terminal.
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION 6.10 Outputs – Volt Free Relay Non-Programmable Definition: A relay with voltage free change over contacts for user connections. 6.10.1 Fault Output TB5 8/9/10 The relay is de - energised in any fault condition. All faults except “System Faults” are non-latching. The contacts are rated at 1A 30VDC. This output is not monitored. 6.10.
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION 7 Adding Control and Monitoring Facilities The addition of or a combination of the modules, boards / cards listed below mounted on the back pan or the front panel of the FACP provide additional features to a standard panel. All board inputs or outputs are programmable to any combination of zones. Note: Only one of each board type can be installed in any one panel. The board types are; 1.
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION 7.3 Terminating the Communications Bus + - RS485 Front Panel Card 1 CN9 Front Panel Card 2 BUS 1 ( B1 ) Note: If Backpan boards AND remote facilities are fitted the front panel cards are not terminated K1 Backpan BRD 1 CN5 Fit K1 if only the Main Control Card is used as the FACP or 1 Bus is used.
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION 8 Internal Terminal Block Numbering Quick Reference Terminal Block TP Number TB2/1 2 3 28 29 TB3/1 2 3 4 25 26 27 TB13/1 2 3 4 5 6 7 8 TB14/1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 TB4/1 2 3 4 5 6 7 8 17 18 19 20 21 22 23 24 TB5/1 2 3 4 25 26 27 28 5 6 7 8 9 10 TB12/1 2 3 29 30 31 32 33 34 35 36 37 EN54 COMMUNICATIONS EXTERNAL RS485 + RS485 Shield INPUTS Common Spare Class Change Alert ZONES ( 24mA / Zone ) + Zone 1 - Zone
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION 9 Status and Programming Screens The following shows all the screens that are possible in the FACP and how to navigate through them. I f a screen is not available it means that option has not been installed or is not available to the model in use. Operating Main Menu LEVEL 1 STATUS 9.
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION 9.
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION 9.
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION 9.
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION 10 List of Compatible Devices The following range of devices have been approved to be used with the ZoneSense PLUS.
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION 10.
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION 11 Glossary of Terms ACF: ACKD: AH: AHU: ALM: ASE: AVF: AZF: AZC: COM: CIC: CN: C/O: CPU: DGP: EARTH: EOL: FACP: FDS: FFF: FLT: FP: GND: Ia: Ida: Idd: Iq: I/O: LCD: LCS: LED: MAF: MCP: MOV: NIC: N/C: N/O: PCB: P/S: PSM: REM: SPOT: TB: VDC: ANCILLARY CONTROL FACILITY ACKNOWLEDGED AMP HOUR AIR HANDLING UNIT ALARM ALARM SIGNALLING EQUIPMENT ALARM VERIFICATION FACILITY ALARM ZONE FACILITY ALARM ZONE CIRCUIT RELAY COMMON CONTACT (WIPER) CONTROLLER INTERFA
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION 12 Definitions Addressable system - a fire alarm and detection system that contains addressable alarm zone facilities or addressable control devices. Alarm Signalling Equipment (ASE) – circuitry that provides the necessary indication to the monitoring service providers.
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION 13 Battery Capacity Calculation INTRODUCTION The standby power source capacity, or battery capacity, determines how long the system will continue to operate in the event of the loss of the primary power source. It therefore becomes necessary to calculate the battery and hence power supply / battery charger capacity required for each installation.
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION POWER SUPPLY & BATTERY CALCULATOR Criteria Panel Configuration Example Iq Calculation No Off X mA Iq = Iq Iq Calculation No Off X mA Iq = Iq Basic 4 zone panel Basic 8 zone panel 40.5 1 40.5 40.
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION Criteria Battery capacity at end of battery life = = Note: ☞1,000ma = 1 Amp New battery capacity requirement Example ( Iq x 24 ) + ( Ia x 0.5 ) Note: the figure of 24 above should be 96 if Agent Release is used. = = Ah = = ( Iq x 24 ) + ( Ia x 0.5 ) ( rounded ) ( 100mA x 24 ) + ( 390mA x 0.5 ) = = 2400mA + 195mA = 2595 2.595 Ah = Ah x 1.25 = 2.595 x 1.25 = Ah = 3.24 Ah Rounded up to nearest available Ah 3.
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION 14 Trouble Shooting Chart Problem No Mains Power Supply fault LED illuminated Earth Fault LED illuminated System Fault LED illuminated Warning System Fault LED illuminated RS485 Communication Loop not working Can not access a menu Forgotten Password Alarm Fault Solution Check mains Fuse Check output voltage it should be set to 27.2V. Low = (less than 26.
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION 15 Installation and Commissioning Report This ZoneSense PLUS Fire Alarm Control Panel is installed at: Company Name Street Suburb State / Country Postcode (Company Name & Installation Address) Owner or Owners' Authorised Representative: Company Name Street Suburb State / Country Postcode Type of Installation: NEW MODIFIED ADDITION UPGRADE (Please Circle) Date of commissioning tests: / Name and address of commissioning company, (in 'BLOCK
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION 15.1 Procedure The following tests are the minimum that should be performed when commissioning a system using the ZoneSense PLUS Fire Alarm Control Panel. Supplements to these tests may be added by way of attachments or notation (using waterproof ink) to this documentation. If supplements or tests are added reference to them shall be made at an appropriate point on this document.
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION es Y No N/A 7. Detector testing to be carried out as follows: i Test each installed detector or sampling point with an approved in-situ tester, and ensure that each detector has operated in the correct range, and the alarm has indicated on the control and indicating equipment and, if applicable, at the detector tested.
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION es Y No N/A 12. Alarm Signalling i Check that the master alarm facility is able to receive the alarm signal by operating each alarm zone facility. ii Check that the master alarm facility initiates an alarm to the fire control station equipment. 13. Battery Supply i Check that both the primary and secondary power sources are of a suitable type and capacity.
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION 16 Statement of Compliance Please PRINT Name of building Address Fire Alarm Control Panel Brand Name I/WE have installed in the above building an alteration to the system manufactured by, OR a system manufactured by Name of Service Provider The system is connected to Monitoring service provider by a permanent , non-permanent connection ( Date of connection tick) / / No Ancillary equipment installed / connected to the control and indica
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION hereby certify that the installation has been thoroughly tested from each actuating device and that a test of the transmission of the alarm signal to the monitoring service provider has been satisfactorily carried out. I/We further certify that the whole system and all components in connection therewith are installed entirely in accordance with the current appropriate local requirements.
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION 17 Installation Details # Alarm Zone # Indicate with a number in brackets the number of actuating devices in concealed spaces.
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION 18 Certification Information The ZoneSense PLUS is designed and manufactured by: AMPAC TECHNOLOGIES PTY LTD 7 Ledgar Rd Balcatta WA 6021 Western Australia PH: 61-8-9242 3333 FAX: 61-8-9242 3334 HEAD OFFICE Manufactured to: Certificate of Compliance Number: Equipment Serial Number: Date of Manufacture: Page 40
ZONESENSE PLUS INSTALLATION, COMMISSIONING & OPERATION 19 Commissioning Of Installed Cards And Boards Confirm a Card / Board is in use and functional at the time of commissioning by ticking the appropriate circle.
ZoneSense Plus Installation Commissioning & Operation 20 EN54 ABS Inner Front Panel Configuration Labelling ZONE 1 2 3 4 5 6 7 8 CONFIGURATION NORM / AVF / NON / SELF / AT1 / AT2 NORM / AVF / NON / SELF / AT1 / AT2 NORM / AVF / NON / SELF / AT1 / AT2 NORM / AVF / NON / SELF / AT1 / AT2 NORM / AVF / NON / SELF / AT1 / AT2 NORM / AVF / NON / SELF / AT1 / AT2 NORM / AVF / NON / SELF / AT1 / AT2 NORM / AVF / NON / SELF / AT1 / AT2 EOL VALUE MCP ZONE No LAM's BELL A 3K3 / 4K7 / 6K8 / 10K / CAP 1/2/3/4/5/
21 Specifications Mechanical Dimensions Metal Cabinet: ( mm ) Dimensions ABS Plastic Cabinet: ( mm ) Note: A Battery Box of the same dimension is available should the FACP be optioned to capacity. Environmental Temperature: Humidity: Mains Input Input Voltage: Protection ( Quick Acting Fuse ): Minimum Cable Requirements: Power Supply Voltage: ( Set to 27.