Specifications

Page 7
ZONESENSE PLUS
OPERATION & PROGRAMMING
4 Level 1 Access
Is a read only menu that allows the operator to reset latched Ancillary Control Facility outputs ( IF
FITTED )
In the event an ancillary device trips out or is operated for some reason the latching control of the
device has to be reset to re-establish normal functionality of that device. Press Enter to reset.
The LCD will display the reset progress as seen below and then return to the Default Screen.
ACF TRIP
RESET
RESET
EXECUTE
Note: Use Cancel at any time to step back out of the current Menu.
interrogate the panel to determine the state of selected outputs; STATUS
view any faults that may be present on the FACP. FAULTS
Note: Use Cancel at any time to step back out of the current Menu.
4.1 STATUS
Status allows the operator to select and view the current state/operating conditions of the active
components listed in the following sub-menu.
Press Enter to view the Status Menu. Press Move Right to move through the menu or Enter
to access the Status sub-menus.
Note: The sub-menu headings are in Italic.
O/Ps
Brigade
Relays
Fire Fan
Snders
I/Ps
Voltage
Software
Bell
Alarm 1
Relays 1 to 8
Fan 1 to 4
Sndrs 1 to 8
1 to 16
Battery volts
Version
Warn Sys
Fault
On
On
On
On
Charger volts
ACF
Isolate
Off
Off
Off
Off
System Volts
ASE
Bat Fail
Isolate
Normal
Alarm
Alarm 2
Off Fault
Fault
Note: these screens are only available if the card, module or board is
fitted to the FACP and it is set to Yes in the System Menu
Outputs
Press Enter then Move Right or Move Left to view the status of the monitored Bell,
Warning System, ACF, ASE, Alarm or Fault Outputs on the Main Control Board.
The LCD readout will indicate if the selected Output is;
On and Normal, or Off and Normal, or Off and Isolated, or On and Isolated, or Output is On
and in Fault, or Off and in Fault.
BELL
OFF / NORMAL
WARN SYS
OFF / NORMAL
ALARM
OFF / FLT
Sample Output Screens
Meaning: The O/P is either On (activated ) and Normal, or Off (de- activated ) and Normal, or
On (activated) and Isolated, or Off (de- activated ) and Isolated.