Specifications
Page 3
ZONESENSE PLUS
OPERATION & PROGRAMMING
Level3: ( Pre-commissioning Password factory set at 3333 )
Level 3 SYSTEM and PROGRAM menus can only be accessed by a set Level 3 password that
can not be deleted.
Panels fitted with a key switch have access to level 2 with the switch enabled and then 3 via the
password. Without the key switch access to level 2 is by opening the door and then to level 3 via
the password.
Note: If the keypad controls are not used for a period of 2 minutes the display will return to the
default screen.
2.3 FireFighter Facility Controls
Note: Any of the buttons within the FireFighter Facility will act as a buzzer mute.
ISOLATE
EXTERNAL
ALARM
External Alarm Isolate Is a dedicated control used to isolate (turn off) the “External
Alarms” output and is not over ridden by any other condition. The LCD Screen will
display the isolate if the ISOLATES / OUTPUTS menu is selected.
ISOLATE
WARNING
SYSTEM
Warning System Isolate Isolates (turns off) the “Warning System” output and is not
over ridden by any other condition. The LCD Screen will display the WARNING
SYSTEM is isolated if the ISOLATE / OUTPUTS menu is selected.
ACK
ALARM
Acknowledge On Alarm the Alarm LED and Zone Alarm LED will flash and the Buzzer
will sound. By pressing Acknowledge the LED’s become steady, the Buzzer will be
silenced and a zone/s can be Isolated or Reset.
RESET
FAULT
Reset The Reset is used to return the control panel back to a normal state from the fire
alarm condition. The Reset button is not to be used for any other purpose and will not
reset an isolated condition.
ISOLATE
ISOLATED
Isolate Isolates or De - isolates a Zone which has been selected using the Zone Select
Menu. Inhibits Alarm and Fault signalling outputs but not LED indications generated by
the corresponding zone. Isolates all acknowledged alarms in a single operation and
operates the fault buzzer if an isolate condition still exists on the panel after 8 hours.
The LCD screens below show an example.
ZONES
X ISOL'D
ZONE 1
ACTIVE
ZONE 3
ACTIVE
ZONE 3
ISOL'D
Press
Isolated Enter Move Right Move Up
To Select Zone To Isolate